Operator Interface - Toshiba G8000 SERIES Installation And Operation Manual

480/480 v 80/100/125/150/225/300/500 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

13

Operator Interface

Table 13.1 shows the functions of the operating buttons on the graphic display panel.
Press an operating button for at least 0.5 seconds to change UPS modes. Press
the reset button for at least 5 seconds to reset the UPS.
The UPS may not respond if the button press is too short.
TABLE 13.1 BUTTON AND INDICATOR FUNCTIONS (See fig. 13.1 and 13.2)
#
Name
1
OPERATION LOCK
2
STOP BUTTON
3
RUN BUTTON
4
FLOAT/EQUAL BUTTON
5
SCROLL UP BUTTON
6
SCROLL DOWN BUTTON
7
RESET BUTTON
8
UPS BUTTON
9
BYPASS BUTTON
10
EPO BUTTON
11
LCD DISPLAY
12
UPS SUPPLY LED
13
CONVERTER LED
14
AC INPUT LED
15
FLOAT CHARGE LED
16
EQUALIZE CHARGE LED
17
BATTERY LED
18
DISCHARGE LED
19
BYPASS INPUT LED
20
WARNING LED
21
FAULT LED
22
INVERTER LED
23
UPS LED
24
AC OUTPUT LED
25
BYPASS LED
G8000 Series Installation and Operation Manual
NOTICE
Function
Enables/disables the buttons RUN, STOP, UPS, BYPASS, FLOAT/EQUAL, and RESET.
Stops the UPS. Transfers to bypass power if available.
Starts the UPS. Transfers the unit from bypass to UPS power.
Changes recharge mode between float charge and equalize charge.
Scrolls the LCD screens up.
Scrolls the LCD screens down.
Reset UPS faults and warnings shown on the LCD. (See Section 13.5)
Transfers from bypass operation to normal operation.
Transfers from normal operation to bypass operation.
"ON" during Bypass Supply.
Displays the operational, status, and warning/fault messages.
"FLASHES" during START or STOP sequence "ON" when operating in inverter mode.
"ON" after DC bus capacitors are fully charged through the converter.
"ON" with nominal AC input. "FLASHES" with AC input under-voltage (85%).
"ON" during float charge.
"ON" during equalize charge or protection charge while battery OH contact open.
"ON" when battery is connected. (aux-contact on)
"ON" during battery discharge.
"ON" with nominal bypass input. "FLASHES" when bypass is under-voltage (85%).
Normally "OFF". "ON" when warning displayed on LCD. "FLASHES" when AC input is abnormal.
Normally "OFF". "ON" when faults occur.
Lamp "FLASHES" during START or STOP sequence. "ON" when inverter is operating.
"ON" when the inverter output is connected to the UPS output.
"ON" with AC output connected to the bypass/inverter sources.
"ON" when the bypass power supplies the load
53