Anchor Bolts - Toshiba G8000 SERIES Installation And Operation Manual

480/480 v 80/100/125/150/225/300/500 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

10.3

Anchor Bolts

Install the anchor bolts to secure the UPS on the floor. See Figure 10.2 for anchor bolt installation detail.
Use 12mm (1/2") diameter anchor bolts. There are 16mm (5/8") diameter holes provided in the UPS base.
See Figure 10.3 for the hole locations and dimensions for the specified UPS models.
4 x 5/16 in. (16 mm)
diameter screw holes
Anchor Bolt
FIGURE 10.2
ANCHOR BOLT INSTALLATION DETAIL
80/100/125 kVA
(See Appendix B)
Back
4 x 0.5 in. - Dia. (12 mm)
Front
29.7 in. (755 mm)
G8000 Series Installation and Operation Manual
4 screw holes
(Side View)
3.0 in. (76 mm)
21.7 in.
(551 mm)
Input Section
(862 mm)
FIGURE 10.3
HOLE LOCATIONS/DIMENSIONS
ON BOTTOM OF UPS
150/225 kVA
(See Appendix B)
Back
4 x 0.5 in. - Dia. (12 mm)
Front
46.1 in. (1171 mm)
300 kVA
(See Appendix B)
Back
8 x 0.5 in. - Dia. (12 mm)
Front
22.5 in.
22.5 in.
(571 mm)
(571 mm)
500 kVA
(See Appendix B)
Back
Output Section
Front
33.9 in.
20.0 in.
22.4 in.
(508 mm)
(568 mm)
12 x 0.5 in. - Dia. (12 mm)
21.7 in.
(551 mm)
25.6 in.
(650 mm)
22.5 in.
(571 mm)
30.0 in.
(762 mm)
20.0 in.
(508 mm)
29