Be trained in rendering first aid.
For further information on workplace safety visit www.osha.gov.
2.4

Factory Authorized Personnel

Factory authorized personnel have been factory trained and certified to install, service, and repair the
UPS. Contact the Toshiba Customer Support Center for assistance in locating the factory authorized
personnel nearest you.
3

Important Safety Instructions

The following contains important instructions that should be followed during the installation, operation, and
maintenance of the G8000 Series UPS.
Please refer to the battery manufacturer's instructions for details on operating, maintaining and/or replacing
the batteries for each system. Keep unauthorized personnel from batteries. Only a certified service
representative with battery experience should perform service on batteries.
Misuse of this equipment could result in personal injury and/or equipment damage.
In no event will Toshiba Corporation be responsible or liable for either indirect or
consequential damage or injury that may come from the use of this equipment.
The UPS system input and output is NOT equipped with an over-current protection device, or an
output disconnection at the AC output. The user should provide circuit breakers between the UPS AC
input (or Bypass input) and the power sources and between the UPS output and the critical load input. The
minimum device ratings are listed in Table 3.1.
C
R
apaCity
80 kVA
480 V/277 V
100 kVA
480 V/277 V
125 kVA
480 V/277 V
150 kVA
480 V/277 V
225 kVA
480 V/277 V
300 kVA
480 V/277 V
500 kVA
480 V/277 V
80/100/150/225/300 kVA Temperature restrictions: The maximum operating ambient temperature is 86 °F
(30 °C) at 1.0 PF, and 104 °F (40 °C) at 0.8 PF. If the UPS is exposed to the same ambient temperature as
the battery system, the maximum operating ambient temperature is 86 °F (30 °C) at 1.0 PF, 90 °F (32 °C)
at 0.8 PF. Table 3.2 lists the nominal battery voltage.
4
CAUTION
TABLE 3.1 UPS MINIMUM DEVICE RATINGS
O
i
B
ated
utput
nput
ReakeR
480 V – 150 A
480 V – 200 A
480 V – 200 A
480 V – 300 A
480 V – 400 A
480 V – 600 A
480 V – 800 A
R
O
B
ating
utput
ReakeR
480 V – 125 A
480 V – 150 A
480 V – 200 A
480 V – 250 A
480 V – 350 A
480 V – 500 A
480 V – 800 A
G8000 Series Installation and Operation Manual
R
ating