Table 3-1: Dip Switch Setting On Parallel Interface Board (Ifau-16*); Figure 3-5: Dip Switch Location On Parallel Interface Board (Ifau-16*); Figure 3-6: Example Of Dip Switch Setting - Toshiba G9000 Series Installation Manual

Mms kit 480/480 v 1000/1330/1500/1660/2000kva
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

Step 8: Setup the dip switch on IFAU-16* according to Table 4-1.
Figure 4-5: Dip Switch Location on Parallel Interface Board (IFAU-16*)
System
2 by MMS
3 by MMS
4 by MMS
5 by MMS
6 by MMS
UPS#1
1 to 8: ON
(All ON)
10
Table 4-1: Dip Switch Setting on Parallel Interface Board (IFAU-16*)
No.1
No.2
UPS
UPS
1 and 2: ON
All ON
3 to 8: OFF
All ON
All OFF
All ON
All OFF
All ON
All OFF
All ON
All OFF
UPS#2 ~ UPS#(N-1)
1 to 8: OFF
(All OFF)
Figure 4-6: Example of Dip Switch Setting
Dip Switch(S1)
No.3
No.4
UPS
UPS
1 & 2: ON
3 to 8: OFF
1 & 2: ON
All OFF
3 to 8: OFF
All OFF
All OFF
All OFF
All OFF
UPS#N
1 and 2: ON
3 to 8: OFF
G9000 MMS KIT Installation Manual 1000-2000kVA – 200150-001
No.5
No.6
UPS
UPS
1 & 2: ON
3 to 8: OFF
1 & 2: ON
All OFF
3 to 8: OFF