FIGURE 23-5
10. Place the removed SWBP on an antistatic mat.
11. Mount the replacement SWBP by following the removal instructions in
and
Caution – Do not forcibly push the SWBP in when inserting it. If the SWBP is
forcibly inserted despite the presence of any obstruction in a slot or any problems
with the connector pin, serious damage may result.
The connector on the left edge of the base plate of the switch BP is not used for the
SPARC Enterprise M8000 server. Be aware of this when connecting cables.
12. Switch on all main line switches for the AC section (ACS) in the power supply
system.
13. Confirm that the XSCF STANDBY LED (green) on the operator panel remains
lit. If it is blinking, wait until it remains lit.
23-8
SPARC Enterprise M8000/M9000 Servers Service Manual • June 2010
Removing the SWBP (Front of the M9000)
Step 9
in reverse order.