13. Start (turn on power) all domains together. Take either of the following two
actions:
Press and hold down (for less than four seconds) the POWER switch on the
operator panel.
From a console that is connected to XSCF, execute the poweron -a command
of XSCF.
The power to all the domains is turned on, and then the power-on self test (POST)
is executed. When ok prompt displayed on the console of relevant domain, POST
is completed.
For details of the power-on operation, see
on page
4-19, and the SPARC Enterprise M3000/M4000/M5000/M8000/M9000
Servers XSCF User's Guide.
14. Confirm that the replacement components are normal by using the
showhardconf or showstatus command of XSCF.
Unless "*" is displayed for the replacement ACS, it is operating normally.
For details of the showhardconf command and showstatus command, see the
SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF User's Guide,
the SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF Reference
Manual, or the man page.
Note – The showstatus command displays information on degraded components.
15. Restore the original mode switch setting on the operator panel.
Note – When the maintenance work is completed, be sure to confirm the mode
switch setting and return the switch to Locked.
16. Close the door on the server, and lock it.
Section 4.4.2, "Powering the Server On"
Chapter 18
AC Section Replacement 18-11