Digital Input Connectors (X1) - Siemens SCALANCE X-400 Operating Instructions Manual

Industrial ethernet switches
Hide thumbs Also See for SCALANCE X-400:
Table of Contents

Advertisement

Installation and Commissioning
6.6.3

Digital Input Connectors (X1)

Polarity Reversal Protection X1, X2
The two 5-pin male connectors (X1, X2) of the digital inputs 1 through 8 have no
polarity reversal protection. If the connectors are accidentally swapped over, this
does not cause damage or destroy circuits. In display modes A and C or B and D,
incorrect inputs are displayed during the time the connectors are swapped over.
Digital inputs 1 through 4 are connected using a 5-pin connector at the front termi-
nal block on the DI module.
Figure 6-11
Conn. 1
Warning
!
The input voltage must not exceed + 30 V and must not fall below – 30 V, other-
wise the DI module will be destroyed.
92
Pin assignment of connector X1 (Inputs 1 through 4)
IN1
Digital input 1
IN2
Digital input 2
M4
Ground
IN3
Digital input 3
IN4
Digital input 4
Operating Instructions for SCALANCE X-400 Industrial Ethernet Switches
C79000-G8976-C186-03