Product Description of SCALANCE X-400
Startup Behavior
C-PLUG
1
not found
2
empty
3
written with own X414-3E configu-
ration data.
4
written with third-party X414-3E
configuration data.
5
written with configuration data of a
different device type.
6
defective
In cases 1 and 2, the configuration data on the Switch CPU and the C-PLUG is
identical. In cases 3 and 5 the configuration data is different and can be synchro-
nized manually. In case 6, you can attempt to reformat the C-PLUG with the clean
function. If problems persist, replace the C-PLUG.
Notice
In case 4 (replacing the switch), the DIL switch settings of the C-PLUG and not the
physical switch settings are adopted. A deviation is signaled by the diagnostic op-
tions.
For more detailed information, refer to the SCALANCE X-400 Configuration Man-
ual .
46
X414-3E Startup
with internal configuration (if it exists)
or with factory defaults.
with internal configuration, immediately
copies this automatically to the C-
PLUG.
with C-PLUG configuration.
with third-party C-PLUG configuration.
with internal configuration, red LED on
power module and log entry.
with internal configuration, red LED on
power module and log entry.
Operating Instructions for SCALANCE X-400 Industrial Ethernet Switches
C79000-G8976-C186-03