Function description
Additional function for DHW heating
Make the following settings at the
solar control unit:
1. Main menu
■ "System"
■ "Options"
– "Add. fct."
Set "Yes".
2. Select the appropriate sensor for
capturing the temperature (delivered
condition S2) subject to which con-
sumer this function should affect:
Main menu
■ "System"
■ "Contractor"
– "Sen. add.fct."
Set value "1" to "12".

Cylinder heating

■ To achieve the heating of a consumer
within a specific range, the sensors for
functions "Thermost. 3" and "Ther-
most. 4" (in the delivered condition S5
and S6) are required. These may be
switched to sensors that are already in
use (see page 161).
■ Reference parameters are the start
temperature "Th3on" and the stop
temperature "Th3off".
■ Relay R6 on:
When "Th3on" is not reached at either
sensor.
■ Relay R6 off:
When "Th3off" is exceeded at both
sensors.
■ In addition "Timer switch 2" (see
page 159) can be activated for this
function.
138
(cont.)
3. The transfer pump starts at an adjust-
able time "t-start" (delivered condi-
tion 17:00 h), if the consumer has not
reached 60 ºC at least once per day.
Main menu
■ "System"
■ "Setting values"
– "t-start"
Delivered condition 17:00 h
Set the start of the additional
function.
Make the following settings at the
solar control unit:
1. Main menu
■ "System"
■ "Options"
– "DHWcyl.load."
Set "Yes".
2. Main menu
■ "System"
■ "Contractor"
– "Sen.Th3"
Delivered condition 5
Select sensor.
– "Sen.Th4"
Delivered condition 6
Select sensor.