Electronic temperature differential control unit
Table of Contents

Advertisement

System examples
System example 1
■ Actual temperature dropping below
the stop temperature differential ΔToff
■ Exceeding the electronic temperature
limit of control unit eZ (max. 90 °C)
■ Reaching the temperature selected at
high limit safety cut-out qW (if installed)
Additional function for DHW heating
The requirements for the additional func-
tion are achieved through circulation
pump R5 qT.
Suppression of DHW cylinder reheat-
ing by the boiler
Coding address "67" in boiler control unit
2 defaults a third set DHW temperature
(setting range 10 to 95 °C). This value
must be below the first set DHW temper-
ature. DHW cylinder qP will only be
heated by boiler 1 (solar circuit
pump R1 eE runs) if this set value cannot
be achieved by the solar thermal sys-
tem.
10
(cont.)
DHW heating without solar energy
The upper section of DHW cylinder qP is
heated by boiler 1. The cylinder ther-
mostat with cylinder temperature sen-
sor 3 of boiler control unit 2 regulates
circulation pump for cylinder heating
4.