Fault messages
Very large temperature differential between the collector array and consumers
during operation (heat cannot be dissipated):
Solar circuit pump faulty? ⇒
No
Solar heat exchanger scaled up? ⇒
No
Solar heat exchanger blocked?
No
Yes
Solar heat
Flush the solar
exchanger
thermal sys-
sized too small.
tem (see col-
lector service
instructions).
The solar circuit pump does not run, although the temperature in the collector
array is higher than that in the consumer.
Display dark?⇒
Yes
■ Check the operating voltage (ON/OFF
switch, power cable).
■ Check fuse F1, 6.3 A (slow).
If fuse F1 is faulty; replace it (see
page 93).
(cont.)
Yes
Descale solar
heat
exchanger.
Yes
Check the solar circuit pump:
■ Check the operating voltage
(ON/OFF switch, power
cable).
■ Check fuse F1, 6.3 A (slow).
If fuse F1 is faulty; replace it
(see page 93).
No
Check whether the solar circuit pump
runs in manual mode (see page 84).
No
Is pump current enabled
by the solar control unit?
No
Yes
Check fuse
Solar circuit
F1, 6.3 A
pump
(slow).
seized.
If fuse F1 is
Free the
faulty;
pump shaft.
replace it
Replace the
(see
pump if it
page 93).
refuses to
Otherwise
run.
replace
solar con-
trol unit.
Troubleshooting
Yes
Start tem-
perature dif-
ferential
"ΔTon" too
great?
If yes,
change
value (see
page 151).
91