Viessmann VITOSOLIC 200 Installation And Service Instructions Manual page 46

Electronic temperature differential control unit
Table of Contents

Advertisement

System examples
System example 6
Control unit, freshwater module
qP
qE
qW
Required settings on the solar control unit
Main menu
Operator code
Solar options
■ System (see page 95)
Set solar values
■ Tcylset (set cylinder temperature)
■ ΔTon (start temperature differential for solar circuit
pump R1 eE)
■ ΔToff (stop temperature differential for solar circuit
pump R1 eE)
System options
■ ΔT Fct6 (ΔT function for switching the three-way
diverter valve R6 rZ, function block 2, see
page 112)
46
(cont.)
N
?
L N
M
1~
L
N
?
qQ
230 V / 50 Hz
Delivered
condition
0000
60 °C
8.0 K
4.0 K
Setting
0200
1
1
No