Viessmann VITOSOLIC 200 Installation And Service Instructions Manual page 144

Electronic temperature differential control unit
Table of Contents

Advertisement

Function description
Heat statement
■ Statement:
Through determining the temperature
differential between the flow and
return temperature and the throughput
captured by the flow meter.
■ Sensor inputs S1 and S10 to S12 are
provided in the delivered condition for
this purpose.
Should the flow temperature sensor
have to be located at a point where
temperatures in excess of 90 °C could
occur, always connect it at S1 or S9
(NTC sensor with 20 kΩ) (see also
page 69).
Note
Sensors that are already installed may
be used.
These must be switched over (see
page 161).
Make the following settings at the
solar control unit:
1. Main menu
■ "HM"
■ "Options"
– "HM 1" or "HM 2"
Set "Yes".
Flow meter
Pulse rate
Standard flow rate
144
(cont.)
06
l/imp
1
3
0.6
m
/h
2. Main menu
■ "HM"
■ "HM 1" or "HM 2"
■ "Contractor"
– "Sen. Flow"
Select the sensor to be used (S1
to S12).
– "Sen. Return"
Select the sensor to be used (S1
to S12).
– "Frostprot.type"
Set the value for the heat transfer
medium selected.
– "Frost protection"
Select the mixing ratio of the heat
transfer medium.
– "Flow transm"
Set "Yes".
– "Vol./Imp."
Delivered condition 1 l/Imp
Set the pulse rate suitable for the
flow meter (see the following
table).
15
25
10
25
1.5
2.5
35
60
35
60
3.5
6.0