4-WIRE SMOKE DETECTORS

4-WIRE SMOKE DETECTOR WIRING
29
28
( - )
2-WIRE SMOKE DETECTORS
2 -W IR E S M O K E
D E T E C T O R W IR IN G
26
27
28
X
GEM-P3200 Installation Instructions
The GEM-P3200 can use conventional 12 VDC 4-wire smoke detectors. To use them, the
select fire zone programming option and do not select 2-wire smoke detector
programming option for the desired fire zone (refer to the GEM-P3200 Programming
Instructions). Set JP7 to the BURG position as shown, if zones 7 or 8 are to be used.
Four wire smoke detectors may be connected to any programmed fire zone (1-8) as
shown, within the panel. If external EZMs are used for zones 9-32, then 4-wire smoke
detectors may be connected to any programmed fire zones (9-32).
Power must be obtained from terminal 28 (+) and 29 (-). If Fire Alarm Verification is
desired to reset the smoke detectors, select this option for the desired fire zone.
NOTE: Do not program Fire Alarm Verification in California
Two-wire smoke detectors may be connected to control panel zones 7 and 8, which
are configured for 2 wire fire through the JP7 jumper settings. To enable, program
the zone(s) as Fire Zones, enable 2-Wire Fire (refer to the GEM-P3200
Programming Instructions) and set JP7 to the position as shown. Connect the
2-wire smoke detectors as shown.
If Fire Alarm Verification is desired to reset the smoke detectors, select this option
for the desired fire zone (zone 7 or 8).
NOTE: Do not program Fire Alarm Verification in California