Four-Wire Smoke Detectors. If installing 4-wire smokes, subtract smoke-detector alarm current from available standby current. See
COMPATIBLE UL-LISTED DEVICES.
Wire 4-wire smokes as shown in the following wiring diagram. Program each zone for Fire. Also program zones for Pulse Burglary
Output, and Disable Fire Reset in the applicable area(s) (System Options). If they are of the self-resetting type, 4-wire smokes may be
powered from Terminals 13 and 14 (AUX. PWR.) instead of Terminal 28 and 29, thus freeing the Reset Relay for other uses.
Split Reporting See Report Telco 3
Start Exit Delay After Ringback
When a closing report is successfully received, the central station will acknowledge by returning a kissoff signal. When the kissoff
is received by the communicator, a 2-second ringback tone will sound at the keypad. Start Exit Delay After Ringback will cause the exit
delay to start after the ringback sounds.
If this option is chosen and no ringback sounds shortly after the control panel is armed, exit delay will not start and opening the
exit/entry door will cause an instant alarm. To manually start the exit delay, select the START EXIT TIME function, then press the
J
button to execute.
Note: (1) If this feature is selected, Exit/Entry Follower Zones will not arm until either a ringback sounds or the START EXIT TIME
function is used. (2) If communicator, telephone lines or central-station receiver is out of service, the system will be armed without
communication capability.
Status Report See Closing Report
Subscriber Identification Numbers
X
GEM-P3200 Installation Instructions
Connecting 2-wire smoke detectors to zones 7 & 8
Additional 4-wire smokes
Wiring diagram, 4-wire smoke detectors
WI817C 08/00