GEM-RP1CAe2/GEM-K1CA Keypad Easy Program Menu
o create a custom program using the GEM-RP1CAe2/GEM-K1CA keypad, simply answer the following questions and record
T
your information on the Easy Menu Programming Worksheet. In each of the following steps, press
NEXT/YES button to go forwards, the PRIOR/NO button to go backwards,
# o f Z n s i n A r e a 1
E n t e r # Z o n e s X X
(Direct Entry)
F i r e
Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
2 - W i r e F i r e Z n s
En ter Zone #
° °
(Direct Entry)
R e p o r t A l l Z o n e s
T o C e n t r a l ? Y / N
(Press YES or NO)
E x i t / E n t r y Z o n e s
E n t e r Z o n e #
(Direct Entry)
I n t e r i o r Z o n e s
E n t e r Z o n e #
(Direct Entry)
2 4 H o u r Z o n e s
E n t e r Z o n e #
(Direct Entry)
X
GEM-P816 Programming Instructions
Total Number of Zones in Area 1 (New Program Only)
Enter the total number of zones to be programmed for Area 1.
Valid entries are from 01 to 32. Directly enter the total number of zones, including leading zeros.
The system is based on groups of 4 zones each (after the first 8 zones), and will automatically
round up to the next group of 4. For example, if you enter 18, it will automatically convert this to
U
20 zones. Press
to save. Press the NEXT/YES button to proceed.
Fire Zones in Area 1 (New Program Only)
Enter the zone number of any Fire Zones (including 2-wire, 4-wire or wireless).
Valid entries are from 01 to 32.
Directly enter each zone number, including leading zeros, and press
peat for any additional zone(s). Press the NEXT/YES button to proceed.

2-Wire Fire Zones in Area 1

Enter the zone number of any Fire Zone (from previous question) to be used with 2-wire
smoke detectors.
Valid entries are 07 and 08. Directly enter each zone number, including leading zeros.
U
Press
to save, and repeat for any additional zone(s); press NEXT to proceed.
NOTE: Only zones which have been designated as Fire Zones can be programmed as 2 Wire
Fire zones. JP3 must be set to "2-WF" position for 2-wire fire. (refer to Installation Instructions).
Local or Central Station Reporting System (New Program Only)
Press the NEXT/YES button for all zones to report; press the PRIOR/NO button for local system
Exit/Entry Zones in Area 1 (New Program Only)
Enter the zone numbers of zones to be used as Exit/Entry zones.
X X
Valid entries are from 01 to 32. Directly enter each zone number, including leading zeros.
U
Press
to save and repeat for any additional zone(s); press the NEXT/YES button to proceed.
NOTE: Exit/Entry Entry time of 30 seconds will automatically be programmed.
Interior Zones in Area 1 (New Program Only)
Enter the zone numbers to be used as Interior Zones.
X X
Valid entries are from 01 to 32. Directly enter each zone number, including leading zeros.
U
Press
to save and then repeat for any additional zone(s).
Press the NEXT/YES button to proceed.
All Interior zones will also be automatically programmed as "Exit/Entry Follower" and as
"Power Up Delay" zones.
24 Hour Zones in Area 1 (New Program Only)
Enter the zone numbers of zones to be used as 24 Hour zones.
° °
Valid entries are from 01 to 32. Directly enter each zone number, including leading zeros.
U
Press
to save and repeat for any additional zone(s); press the NEXT/YES button to proceed.
NOTE: 24 Hour Zones will automatically be programmed as audible (Burg Output).
U
to save and
C
(New Program Only)
L
WI995C 2/04
to set cursor, the
R
twice to exit at any time.
U
to save, and then re-
NAPCO Security Systems