Wiring; Wireless Systems; Typical Residential Fire Installation; Typical Partitioned Installation - NAPCO Gemini GEM-P3200 Installation Instructions Manual

Control panel/communicator
Hide thumbs Also See for Gemini GEM-P3200:
Table of Contents

Advertisement

!
Page 10

WIRING

Wire keypad(s), zones, expansion zone modules and output devices as shown on the Wiring Diagram. Note that the
Wiring Diagram contains important information not available elsewhere in this manual.
CAUTION: Do not run telephone wiring near speaker wires; do not run keypad wiring with loop wiring.
Adding Expansion Zones
GEM-P3200 Series control panels will handle up to 8 zones as is, however this number may be increased to as many as
32 programmable zones using optional expansion zone modules (EZMs).
WIRELESS SYSTEMS (NOT EVALUATED BY U.L.)
With the addition of at least one GEM-RECV series receiver, the GEM-P3200 will support up to 48 wireless transmitters.
The panel can accommodate one to four receivers within the premises, responding to the one with the stronger
transmitter signal. If any transmitters are selected for the default program, a GEM-RECV receiver will automatically be
programmed.
The keypad can display the status of any transmitter, indicating the condition of the zone (normal or open) and transmitter
troubles (low battery, tamper or supervisory failure), and signal strength of the last transmission. A receiver failure will be
indicated by "E06-NN" ("no response", with NN representing the receiver number).
TYPICAL RESIDENTIAL FIRE INSTALLATION (WHERE PERMITTED BY
Refer to NFPA Standard No. 74 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269) for
additional information, including proper mounting of detectors.

TYPICAL PARTITIONED INSTALLATION

fire alarm audible device be installed indoors. The User Program Code is not to be given to anyone except the authority responsible
for all partitions.
X
GEM-P3200 Installation Instructions
LOCAL CODES)
At least one smoke detector should be installed directly outside
each sleeping area. If there is more than one floor, additional
smoke detectors should be installed on each level, including the
basement. The living-area and basement smoke detectors should
be installed near the stairway of the next upper level.
For increased protection, additional detectors should be installed
in areas other than those required, such as the dining room,
bedrooms, utility room, furnace room, and hallways. Heat
detectors, rather than smoke detectors, are recommended in
kitchens, attics, and garages due to conditions that may result in
false alarms and improper operation. Large areas and areas with
partitions, ceiling beams, doorways, and open joists will require
additional detectors.
Described and illustrated here are an example of a partitioned system
with common-area protection of the control-panel room. This system
meets UL requirements for a partitioned installation.
!
Both areas must be owned and managed by the same person(s).
!
Both areas must be part of one building at one street address.
!
The control panel and all wiring protecting each partitioned area must be
confined to the respective area and may not encroach upon the other area. This
requires that the control panel room have redundant protection; that is (a)
multiple sets of door contacts, each wired to a separate zone and (b) one of
those zones programmed for each area. In order to gain access to this protected
area without causing an alarm, both partitions must be disarmed. In lieu of
redundant protection, 24-Hour Zones may be used. Any zone protecting the
control panel and transformer may not be programmed for bypass.
The sounding device must be placed such that the bell test can be heard by all
partitions. Note: NFPA 74 (Household Fire Warning Equipment) requires that a
WI817C 08/00
L
NAPCO Security Systems

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents