Reset Relay See Alarm Outputs
Resound on Wireless Smoke Low Battery
If a wireless smoke detector low battery is detected, it will re-sound the trouble at the keypad every 4 hours when disarmed and
every 12 hours when armed, until the condition is corrected.
RF Jam Reporting
RF Receiver Jam will report as RF Receiver Trouble.
Silence All Outputs During Audio Session with Lug E19
Whenever an active low is applied to control-panel Lug E19 (Listen-In), all output relays will turn off. Connect Veri-Phone Terminal
16 (INHO) to Lug E19.
Selective Bypass
Disable Code Required for Easy Bypass (Not for UL installations.)
Any or all zones (1–48) programmed for Selective Bypass may be removed from the system, but each must be removed
separately. Refer to BYPASSING ZONES in Section 3 for operation.
Security Bypass, recommended for commercial applications, requires entry of a valid user code.
Easy Bypass, recommended for residential applications, is selected by programming Disable Code Entry for Easy Bypass; this
will permit bypassing/unbypassing zones without the need of entering a code (see Easy Bypass in Section 3). Do not program this
feature in high-security applications.
When one or more zones is bypassed, the "BYPASSED" reminder on the GEM-RP1CAe2 keypad will display.
Sensor Watch
Program for any zone containing a PIR or dual-technology sensor, floor mats, door contacts, or other device where some activity
is expected. This feature supervises the sensor by verifying that the zone activates before the PIR timer runs out. If no trip is detected
within the programmed Sensor-Watch time, a system trouble will result and "E22-NN PIR SENSOR TRBL" will be displayed at the keypad,
where NN are the zone number(s). Select the RESET SENSOR MSG function to reset this system trouble.
Program the Sensor-Watch PIR timer in Location 4088. Select a value in accordance with the anticipated activity within the
coverage area while disarmed. In calculating the Sensor-Watch time, note that only the disarmed hours (the time between armed
periods) are added. In moderate traffic areas, a Sensor-Watch time of perhaps 1 hour may be appropriate, whereas in remote areas,
a time of 8 hours or more may be in order. Supervision time should be calculated for the supervised zone with the least amount of
traffic. Up to 255 hours may be programmed (see Time Selection).
Silence All Outputs During Audio Session See Veri-Phone
Single-Digit Format See Data Format
Smoke Detectors
Connect smoke detectors as shown in the following diagrams. The normally-closed contacts of the Reset Relay are used to reset
the smoke detectors.
Two-Wire Smoke Detectors. Two-wire smoke detectors may be connected to zones 1-8 on the control panel. Up to 10
compatible 2-wire smoke detectors may be wired to each zone. In Residential applications, program Pulse Burg Output. Program
Disable Fire Reset in the applicable area(s).
Zones 7 and 8 have been designed so they can be easily configured as 2-wire smoke detector zones by means of jumpers (JP7)
located above Terminal 21.
1. Program Zones for 2-Wire Smoke Detectors and Fire.
2. If Zone 7 is selected as a 2-Wire Fire Zone, move the left jumper on JP7 from the top two pins (BURG) to the bottom two pins
(2WF).
3. Similarly, if Zone 8 is selected as a 2-Wire Fire Zone, move the right jumper on JP7 from the top two pins (BURG) to the bottom
two pins (2WF).
4. Connect 2-wire smoke detectors to Zones 7 and/or 8 as shown.
L
NAPCO Security Systems
X
GEM-P3200 Installation Instructions
!
Page 45