Page 26
DISPLAY FIRE TRBL
To display Fire Zone(s) in trouble, access DISPLAY FIRE TRBL and scroll through the zones using the
Correct the problem, then press the
DISPLAY OP/CL
NAPCO's PCD3000 Quickloader software offers a comprehensive array of programmable opening and closing
suppression windows, by area, for all days of the week, for both normal and holiday schedules. A two-line display of the
programmed schedule may be read at the keypad. The first line indicates:
!
the day of the week
!
opening or closing suppression window
!
"AUTO", if autoarming
!
normal (or delayed) schedule (see below)
To scroll through the days of the week, use the
be delayed up to four hours at the keypad, or the window may be totally disabled, up to one week in advance. Select the
DAY/OP/CL schedule using the
Note: If the schedule includes autoarming, arming will be delayed accordingly. Also see Autoarm Function. (Autoarming
can be disabled or delayed by area using PCD3000 software.)
ACTIVATE OVERVIEW
This mode provides a system status display of both partitioned areas at a glance. Note: The keypad selected for the
Overview Mode will remain in that mode. To convert the keypad back to its original use as an area keypad, enter the
Function Mode and access DEACTIVATE OVERVIEW. The display will revert to "SYSTEM READY". Also see Overview
Mode.
ACTIVATE CHIME *
Press YES (
button) to sound a tone at the keypad when a Chime Zone is violated. The duration of the tone is
E
programmable. To turn off the Chime Mode, press YES (
ACTIVATE WATCH*
This option, if programmed, permits all zones designated as Day Zones to be turned on. When selected, a "W" will
appear in the display (GEM-RP1CAe2 only) as long as the Watch Mode is active. To deactivate the Watch Mode, arm,
then disarm.
RESET SYSTEM TRBL
System troubles normally latch and display and sound at the keypad. Pressing the
"SYSTEM READY" will be displayed. Correcting the trouble will clear most system trouble indications, however the following
system troubles require a Level-2 or -3 code for manual reset (enter code; access RESET SYS TRBL then press the
J
button.)
!
EZM Tamper
!
Keypad Tamper
!
Sensor Watch
!
Service Reminder
Note: (1) If a system trouble is not corrected, it will redisplay after 5 minutes. (2) If one or more of the foregoing system
troubles appear during the first 5 minutes after power-up, they will be cleared automatically.
RESET SENSOR MSG
Press YES (
button) to reset a PIR Supervision system trouble.
E
X
GEM-P3200 Installation Instructions
button to restore the "SYSTEM READY" condition.
C
and
E
and
buttons. Select the delay (1-4 hours) or disable using the
E
F
E
buttons. The closing of any suppression window may
F
button) at the DEACTIVATE CHIME function.
C
L
WI817C 08/00
button.
E
J
button.
button will silence the sounder;