Gem-Rp1Cae2/Gem-K1Ca Easy Program Menu; Total Number Of Zones In Area 1; Fire Zones In Area 1; 2-Wire Fire Zones In Area 1 - NAPCO Gemini GEM-P816 Programming Instructions Manual

Table of Contents

Advertisement

Page 6
GEM-RP1CAe2/GEM-K1CA Keypad Easy Program Menu
o create a custom program using the GEM-RP1CAe2/GEM-K1CA keypad, simply answer the following questions and record
T
your information on the Easy Menu Programming Worksheet. In each of the following steps, press
YES button to go forwards, the PRIOR/NO button to go backwards,
# o f Z n s i n A r e a 1
E n t e r # Z o n e s X X
(Direct Entry)
F i r e
Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
2 - W i r e F i r e Z n s
E n t e r Z o n e #
(Direct Entry)
R e p o r t A l l Z o n e s
T o C e n t r a l ? Y / N
(Press YES or NO)
E x i t / E n t r y Z o n e s
E n t e r Z o n e #
(Direct Entry)
I n t e r i o r Z o n e s
E n t e r Z o n e #
(Direct Entry)
2 4 H o u r Z o n e s
E n t e r Z o n e #
(Direct Entry)
GEM-P816 Programming Instructions
Total Number of Zones in Area 1 (New Program Only)
Enter the total number of zones to be programmed for Area 1.
Valid entries are from 01 to 16. Directly enter the total number of zones, including leading zeros.
The system is based on groups of 4 zones each (after the first 8 zones), and will automati-
cally round up to the next group of 4. For example, if you enter 18, it will automatically con-
vert this to 20 zones. Press
Fire Zones in Area 1 (New Program Only)
Enter the zone number of any Fire Zones (including 2-wire, 4-wire or wireless).
Valid entries are from 01 to 16.
Directly enter each zone number, including leading zeros, and press
peat for any additional zone(s). Press the NEXT/YES button to proceed.
2-Wire Fire Zones in Area 1 (New Program Only)
Enter the zone number of any Fire Zone (from previous question) to be used with 2-wire
° °
smoke detectors.
Valid entries are 07 and 08. Directly enter each zone number, including leading zeros.
U
Press
to save, and repeat for any additional zone(s); press NEXT/YES to proceed.
NOTE: Only zones which have been designated as Fire Zones can be programmed as 2 Wire
Fire zones. JP3 must be set to "2-WF" position for 2-wire fire. (refer to Installation Instruc-
tions).
Local or Central Station Reporting System (New Program Only)
Press the NEXT/YES button for all zones to report; press the PRIOR/NO button for local sys-
tem
Exit/Entry Zones in Area 1 (New Program Only)
Enter the zone numbers of zones to be used as Exit/Entry zones.
X X
Valid entries are from 01 to 16. Directly enter each zone number, including leading zeros.
U
Press
to save and repeat for any additional zone(s); press the NEXT/YES button to proceed.
NOTE: Exit/Entry Entry time of 30 seconds will automatically be programmed.
Interior Zones in Area 1 (New Program Only)
Enter the zone numbers to be used as Interior Zones.
X X
Valid entries are from 01 to 16. Directly enter each zone number, including leading zeros.
U
Press
to save and then repeat for any additional zone(s).
Press the NEXT/YES button to proceed.
All Interior zones will also be automatically programmed as "Exit/Entry Follower" and as
"Power Up Delay" zones.
24 Hour Zones in Area 1 (New Program Only)
Enter the zone numbers of zones to be used as 24 Hour zones.
° °
Valid entries are from 01 to 16. Directly enter each zone number, including leading zeros.
U
Press
to save and repeat for any additional zone(s); press the NEXT/YES button to proceed.
NOTE: 24 Hour Zones will automatically be programmed as audible (Burg Output).
U
to save and
twice to exit at any time.
C
U
to save. Press the NEXT/YES button to proceed.
to set cursor, the NEXT/
R
U
to save, and then re-
NAPCO Security Systems
R

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents