Emerson MultiFlex CUB-II Installation And Operation Manual page 75

Condensing unit board
Table of Contents

Advertisement

None, the Input Types to None, and
Offsets to 0 (zero).
3. Press
to exit screen and save
changes, or
screen.
If using an E2, press to exit and save or
 to return to the Home screen.
Figure A-8 - CUB Inputs Setup DropLeg Temperature
CUB Outputs
From the MultiFlex CUB Status screen, press
and
to set up Outputs (press
the MultiFlex CUB Status screen if using an E2).
1. Press
to move to the CUB Out-
puts tab, and set Outputs 1-4 to Con-
denser Fans 1-4, respectively
(depending on the number of fans be-
ing controlled). Press
Up menu (
2. Press
to exit screen and save
changes, or
screen.
If using an E2, press to exit and save or
 to return to the Home screen.
Configuring Setpoints in E2 or Einstein for CUB-TD
to return to the Home
from
for Look
if using an E2).
to return to the Home
Figure A-9 - CUB Outputs
General
From the MultiFlex CUB Status screen, press
and
to access General tab options (press
from the MultiFlex CUB Status screen if us-
ing an E2).
1. Arrow down to the Num Cond Fans
field and set the number of fans to be
controlled. This number should match
the number of condenser fans set in
Outputs under the CUB Outputs tab
(CUB Outputs on page 65).
2. Arrow down to Network Alm field
and set to ENABLE to enable net-
work alarming. If network alarming is
enabled, the CUB output configured
as Alarm type will turn ON when the
network loses communication with
the controller.
For example, Network Alm is set to
ENABLE (Figure A-10), and Output 8 is set as
the Alarm output (Figure A-9).
3. Application names can be user de-
fined. To change the name of the TD
application from the default, arrow up
to the Name field and enter the de-
sired name.
Appendix A: TD Quick Start • 65