Figure A-6 - Spare Analog 5 Input Board/Point
Configuring Setpoints in
E2 or Einstein for CUB-TD
The CUB application in E2 and Einstein
looks the same for both CUB and CUB-TD ver-
sions of the MultiFlex CUB. However, since the
CUB-TD’s functionality is limited to condenser
control, not all parameters visible in the E2 and
Einstein setup screens will apply to the CUB-
TD. If you are setting up a CUB-TD, this section
will walk you through setting up only the inputs,
outputs, and setpoints that pertain to the CUB-
TD.
Inputs
These input points (motor room temp and ple-
num temp) come from Global Data because they
are shared among multiple CUB TDs. Refer to
Set Up Motor Room Temperature and Plenum
Temperature Inputs on page 62 for more infor-
mation about Global Data setup for motor room
and plenum temperature.
1. From the MultiFlex CUB Status
screen, press
and
to set up In-
puts (press
from the MultiFlex
CUB Status screen if using an E2).
2. Press
to move to the Inputs tab,
64 • MultiFlex CUB-II and CUB-TD I&O Guide