The descriptions below describe what the
purpose of each output shown on this screen are.
For each output definition, you may:
• Share the value with another E2 or Einstein in-
put - Enter a controller/application/input address in
the output definition, or press
O Formats to change the definition to a board/point
or fixed value.
• Set up logging or change logging parameters -
Move the cursor into the output definition, and nav-
igate to the Logging Setup screen (
stein, 
in E2).
• Set up generic alarming for a parameter - Move
the cursor into the output definition, and navigate to
the Generic Alarm Setup screen (press
Einstein, 
in E2).
SUCTION PRESS
The current value of the CUB suction pres-
sure input.
SATUR SUCT TEMP
The calculated value of the saturation suc-
tion temperature of the condensing unit system.
DISCHARGE PRESS
The current value of the CUB discharge
pressure input.
DROP LEG TEMP
The current drop leg temperature used for
TD Condenser Control.
TD
The current value of the temperature differ-
ential (drop leg temperature + drop leg offset -
plenum temperature).
OIL PRESS
The current value of the CUB oil pressure
input.
CKT STATE
The current CUB refrigeration state. The
options are: Idle, Refrigeration, Defrost, Drip,
Pump Down, Wash, Door, Fail, or Delay.
CASE TEMP 1 - 6
The six CASE TEMP outputs are equal to
the values of each of the six possible CUB case
temperature inputs. CASE TEMP 1 corresponds
to CUB's case temp #1, etc.
36 • MultiFlex CUB-II and CUB-TD I&O Guide

- Alternate I/

in Ein-

in
CURRENT KW
The current value of the CUB KW input.
BOARD STATUS
The online or offline network status of the
CUB board.
CASE TEMP COMBO
The current combined value of all CUB case
temperature inputs. This will be the same as
CASE TEMP 1 if only one case temp sensor is
present on the CUB.
DOOR SWITCH
The current ON/OFF state of the door
switch.
PEAK TEMP
The highest case temperature recorded dur-
ing the previous defrost cycle.
CLEAN SWITCH
The current ON/OFF state of the clean
switch.
DISCH TEMP
The current value of the CUB discharge tem-
perature.
AN SENS #1 and #2
The values of sensor control inputs #1 and
#2. If a Sensor Control input on the CUB is set to
OAT or motor room temp, this definition will be
pre-defined to point to Global Data's OAT or
SPARE ANLG 1-4 inputs. DO NOT change the
values of these fields if they are already pointing
to Global Data.
COMP PROOF
The current OK-FAIL state of the compres-
sor proof.
PHASE LOSS
The current OK-FAIL state of the phase pro-
tection device.
SUCTION TEMP
The current value of the CUB's suction tem-
perature sensor.