FS-8700-41 Simplex 4100 Driver Manual
3

HARDWARE CONNECTIONS

The FieldServer is connected to the Simplex Device's RS-232 port of device type "COMPUTER", the following port
attributes may be configured specifically for that particular port:
Ensure that these settings correspond to the settings described in section 4 of this document.
3.1

Sim4100 Panel

Setting
Default
Baud Rate
9600
1
Parity
EVEN
Data Bits
8
Stop Bits
1
3.2

Sim4100U Panel

Setting
Default
Options
Baud Rate
9600
75, 110, 134.5, 300, 600, 1200, 1800, 2000, 2400, 4800, 9600, 19200
1
Parity
NONE
ODD, EVEN, MARK, SPACE, NONE
Data Bits
8
7 or 8
Stop Bits
1
1 or 2
The following are the Simplex, recommended connections to be used in cabling between the 4100 and the
FieldServer device. For the computer device, the standard EIA signal description, and the 25 pin (DB25) and 9 pin
(DB9) connector assignments are shown.
4100 Host
4100
Port ATB1
Port BTB2
8
1
6
3
7
2
5
4
4
5
1
Odd or Even parity is recommended (by Simplex) to provide additional error detection at the character level.
2
The driver does not support the Simplex RTS/CTS handshaking model. Therefore deselect the HSHAKE terminal flag or connect CTS to RTS
with a jumper on the 4100 side
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Options
75, 110, 134.5, 300, 600, 1200, 1800, 2000, 2400, 4800, 9600, 19200
ODD, EVEN, MARK, SPACE, NONE
7 or 8
1 or 2
Cable
Signal
DB25 Pin
2
TXD
3
RXD
2
4
RTS
5
CTS
──
7
GND
Computer
Signal
DB25Pin
DB9Pin
RXD
2
2
TXD
3
3
RTS
4
7
CTS
5
8
GND
7
5
Page 6 of 48