Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-39 EST3-ECP APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after January 2012 A Sierra Monitor Company Driver Version: 1.11 Document Revision:...
Page 3 of 25 EST3 DESCRIPTION The EST3 External Communications Protocol (ECP) driver allows the FieldServer to transfer data to and from EST devices over RS-232 or RS-485 (with converter) serial ports using the EST3 ECP protocol. In the EST application the FieldServer always emulates a Client.
ECP Type III with Text Not Supported FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com Description 7-ft Cat5 cable with RJ45 connectors at both ends...
Gateway Type III is recommended. The EST3 panel monitors the quality of communications to the FieldServer and will detect a poor connection. Poor connections are normally caused by inappropriate selection of gateway type, but can also be related to installation quality.
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with an EST3 Server. The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for EST3 communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays”...
WRBC is not recommended, as startup values may be invalid FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com , Port , Timeout...
The write priority has the possible values of Set, Latch, Low, Medium, and High. These are encoded as 00h, 01h, 02h, 03h and 04h respectively. Report and Delta Service: The EST ECP3 Report and Delta services report point status slightly differently. The FieldServer EST3 driver deals with these differences as follows: Appendix A.1.1. Report Service (regular polling): The full 16-bit point status is stored to the Read Map Descriptor’s Data Array.
The EST3 panel is only able to send/accept Acknowledgement when the panel is in Proprietary Mode. Contact EST (Edwards Systems Technology) for information on configuring the panel. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com Page 15 of 25...
MD_Set_Date , DA_Set_Date MD_Set_Time , DA_Set_Time The following Map Descriptor will enable the FieldServer to synchronize its clock with the EST panel clock Map_Descriptors Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , EST_Report_Type , Length MD_SLV_TIME , DA_TIME FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com...
To solve multiple com errors, try adding an IC_Timeout parameter to the Client Side Nodes and set it to 0.5s. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com...
FieldServer as SCADA bytes transmitted and received. The FieldServer acts as a client by inserting requests into its response messages; the EST panel then inserts the requested data into its subsequent polling messages. The bytes transferred in this process are displayed on the FieldServer as PLC bytes transmitted and received.
%02X support. Upload the configuration file, make the necessary changes, download to the FieldServer and cycle power to the FieldServer for the changes to take effect. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com...