Appendix C.2. Error Messages

Error Message
Sim4100:#1 <card><point><sub> invalid for ack.
Read manual.
Sim4100:#2 RTS has been asserted for too long.
Extend timer, check cable uses RTS/CTS or
reconfig 4100 device to suppress hardware
handshaking
Sim4100:#3 sim4100_chan_init() Init with null
chan.
Sim4100:#4 Unknown sim4100_func in csv
<nnn>
Sim4100:#5 Use Ackall function.
Sim4100:#6 ack/ackall/seta/setd must be a
write.
Sim4100:#7 disable/restart/list not implemented
Sim4100:#8 Func=Clistall/Clist, wrbc not allowed
Sim4100:#9 Write ack was not expected.
Sim4100:#10
Invalid
<s><v><a>=(Hex)<%x><%x><%x> <%c><%c><%c>
Sim4100:#11. Error. Array too short. rqd= %d(
max= %d) act= %d. MapDesc= <%s> Data
Abandoned! Subsequent msgs suppressed!
Sim4100:#12 Error.
Subsequent message supressed!
Sim4100:#13
FYI.
Login
Implemented.
Sim4100:#14 MD=%s Addr=%d
SIM4100:#15 FYI. Incoming abandoned. No Map
Desc.
SIM4100:#16 FYI. No Map Desc. Respond with
Error.
SIM4100:#17 FYI. Incoming Abandoned. No Data.
SIM4100:#18 FYI. Incoming Abandoned. (%d)
Sim4100:#19a FYI. Sim4100 Firmware found
(%.2f)
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Description
c-p-s is being used to derive an array offset. The calculation requires
division by the point & the sub and one or both of these values are zero.
If RTS-CTS handshaking has been used then this message is produced if
the driver finds that the RTS has been asserted by the slave device for too
long. The timeout is hard coded at 2.0s.
Requires support from FieldServer Technologies.
The driver has found a value for a sim4100_func keyword that it does not
recognize. Check the CSV file and read Appendix C.1of this manual for a
list of legal keywords.
The sim4100_func keyword has been assigned the value 'ack' but a card-
point-sub has not been specified. Use the ackall function.
You cannot use the rdbc function with these keywords. Use a wrbc
instead.
Please contact FieldServer Technologies if you would like this feature
implemented.
These keywords must be used with a Rdbc
Please report this error to FieldServer Technologies.
point
status
Please report his message to FieldServer Technologies noting the values
in braces.
Check the CSV file Data Array lengths.
Incoming data is being abandoned.
Check the CSV file; there was no matching Map Descriptor for a message.
Function
not
Please contact FieldServer Technologies if you would like this feature
implemented.
A write thru is defined as follows. The FieldServer reads data from a
device and stores it in a Data Array. If a remote device changes the value
in that Data Array, the FieldServer will write the new value to the device
that is being read. This driver does not permit write thru's except when
the data is being updated using CLIST. Refer also to Appendix A.4.3 and
Appendix A.6.2. In versions of the driver up to and including 1.07a a
panic is produced when this message is printed. The message is printed
to a maximum of 10 times and then suppressed.
Check the CSV file; there was no matching Map Descriptor for a message.
If the server can't find a matching MD (i.e. the point being polled for
doesn't exist) then the driver responds with Simplex Error #2.
Check the driver manual and Simplex User Manuals. There is no driver
response to the message received.
Please report his message to FieldServer Technologies noting the values
in braces.
No corrective action is required on your part. The message is printed for
information only.