FS-8700-41 Simplex 4100 Driver Manual
Keyword
Description
Each type of Simplex device reports a different set of attributes
and attribute states/values. Refer to Appendix A.2.1 for more
information. The driver analyses the response from the poll.
When an attribute is recognized, the attribute state is evaluated.
If this is recognized then the driver stores a value, corresponding
to the attribute state, at an array location corresponding to the
attribute. Appendix A.2 provides additional information. The
Show
driver can only recognize attributes and attribute states that it is
programmed to recognize.
The length of the Map Descriptor must be set equal to the array
position of the highest attribute.
Ensure that Map Descriptors using this function do not use
overlapping areas of the Data Arrays. See example in Appendix
A.4.8.
This command allows the user to manipulate the status and/or
priority of a control point
Setd
The port access level must be set appropriately in the Simplex
device otherwise the device returns an error.
This command allows the user to:
Manipulate the status and/or priority of a control point
Modify the value of an analog pseudo point.
Seta
Set the sensitivity of a TrueAlarm sensor
Set the rate-of-rise threshold of a TrueAlarm heat sensor
Select the audio channel of a speaker circuit
This is an unsolicited message sent automatically by a Simplex
device to report a change in point status. The card-point-sub
address format is used to calculate an offset into the associated
Xpoint
Data Array as described in Appendix A.1.
reported determines the value being written into the Data
Array. Refer to Appendix B.4 for more information..
Disable
Not Implemented
Restart
Not Implemented
This command sets and displays the time and date in "user"
format.
As a command it sets the hour minute second of the Simplex
device by getting the values from the Data Array associated with
Time
the Map Descriptor. The first element contains the hour, the
second the minute and the third contains the second. A 24 hour
clock is assumed.
As a query, the data is unpacked into the Data Array in the
format described above.
As a command it sets the hour minute second of the Simplex
device by getting the values from the Data Array associated with
the Map Descriptor. The first element contains the hour, the
second the minute, the third element contains the second, the
Ctime
4th contains the day of the week, the 5th contains the month,
the 6th contains the day of the month and the 7th element of
the array contains the year (value 01 indicates 2001). A 24 hour
clock is assumed.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Function
RDBC
Specify c-p-s in the Map Descriptor.
WRBC
Specify c-p-s in the Map Descriptor.
WRBC
Specify c-p-s in the Map Descriptor.
Passive
The state being
Specify c-p-s in the Map Descriptor.
RDBC (Query) or WRBC (Set)
Do not specify c-p-s in the Map Descriptor.
RDBC (Query) or WRBC (Set)
Do not specify c-p-s in the Map Descriptor.
Page 33 of 48