FieldServer FS-8700-41 Driver Manual page 36

Simplex time recorder company - 4100 computer port protocol
Table of Contents

Advertisement

FS-8700-41 Simplex 4100 Driver Manual
Error Message
Sim4100:#19d FYI. Panel Firmware Rev %.2f may
be incompatible.
Sim4100:#19e FYI. Panel Firmware may be
incompatible.
Sim4100:#20 FYI. Data abandoned! Array too
short. MapDesc= <%s>
Sim4100:#21. Error. Data abandoned! Array too
short c-p-s= %d-%d-%d
Sim4100:#22. FYI. Polling Inhibited.
Sim4100:#23. FYI. Polling Enabled
Sim4100:#25. Error. Data abandoned! Array too
short c-p-s= %d-%d-%d
Sim4100:#26 FYI. Data abandoned! Array too
short.(%d) MapDesc=<%s>
Sim4100:#27. FYI. Sequence Number reset
requested & done.
Sim4100:#28. Error. Bad Sim4100_Func=%d in
MD=<%s>
Sim4100:#29. FYI. Length changed to 1 in
MapDesc= <%s>
Sim4100:#30. FYI. Length changed to 1 in
MapDesc= <%s>
Sim4100:#31. FYI. Length changed to 1 in
MapDesc= <%s>
Sim4100:#32. FYI. Sequence number semi-reset.
Sim4100:#33. Error. Invalid Seq Number.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Description
Message 'b' is printed when version 10 firmware is found in the panel.
Message 'b' is printed when version 11 firmware is found in the panel.
The firmware version found is not one that the driver explicitly supports.
This does not mean the driver will not work but if a feature of the driver
isn't working correctly knowing that the firmware version is not
supported may help diagnose the problem more easily.
No corrective action is required on your part. If however, some you
suspect that the driver is not operating correctly it is important that you
mention seeing this message in the Error Buffer when reporting the
problem.
The format of the firmware version information could not be interpreted
correctly. This may mean that your panel has a firmware version that is
not one that the driver explicitly supports. This does not mean the driver
will not work but if a feature of the driver isn't working correctly knowing
that the firmware version is not supported may help diagnose the
problem more easily.
No corrective action is required on your part. If however, some you
suspect that the driver is not operating correctly it is important that you
mention seeing this message in the Error Buffer when reporting the
problem.
Check the CSV file Data Array lengths.
Check the CSV file Data Array lengths.
Polling is disabled until the port supervision message has been received.
This message can be safely ignored. When the panel sends unsolicited
messages to the FieldServer this message is printed. Polling remains
inhibited until the unsolicited message stream end.
When a stream of unsolicited messages is received from the Simplex
panel then polling is inhibited until the stream ends. When the stream
ends this message is printed. It may be safely ignored.
Check the CSV file Data Array lengths.
Check the CSV file Data Array lengths.
Check the CSV file and driver manual for valid Simplex functions.
Check the CSV file for the correct Map Descriptor function type.
Check the CSV file for the correct Map Descriptor function type.
Check the CSV file for the correct Map Descriptor function type.
Message sequence numbers incorrect. Check Simplex User Manuals, and
driver manuals. Contact FieldServer Technologies for additional support.
Page 36 of 48