Appendix A.4.9. Read Analog Psuedo Points - FieldServer FS-8700-41 Driver Manual

Simplex time recorder company - 4100 computer port protocol
Table of Contents

Advertisement

FS-8700-41 Simplex 4100 Driver Manual
Appendix A.4.9.
Read Anal og Psuedo Point s
Use the Sim4100_func = 'value' to read the values from the analog pseudo points. Refer to Appendix C.4.2 for a list of the analog pseudo points.
// Analog Psuedo points
// Map Descriptor
Map_Descriptor_Name
, Data_Array_Name
# Fire Alarms
, DA_C_144
# Supervisory Alarms
, DA_C_144
# Troubles
, DA_C_144
Excessively Dirty Sensors
, DA_C_144
Dirty Sensors
, DA_C_144
Almost Dirty Sensors
, DA_C_144
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
, Data_Array_Offset
, Function
, Node_Name
, 0
, Rdbc
, Simplex_01
, 1
, Rdbc
, Simplex_01
, 2
, Rdbc
, Simplex_01
, 3
, Rdbc
, Simplex_01
, 4
, Rdbc
, Simplex_01
, 5
, Rdbc
, Simplex_01
Page 27 of 48
, Sim4100_Func
, Sim4100_Card
, Sim4100_Point
, value
, 144
, 0
, value
, 144
, 1
, value
, 144
, 2
, value
, 144
, 115
, value
, 144
, 116
, value
, 144
, 117
, Sim4100_Sub
, Protocol
, Length
, 0
, sim4100
, 1
, 0
, sim4100
, 1
, 0
, sim4100
, 1
, 0
, sim4100
, 1
, 0
, sim4100
, 1
, 0
, sim4100
, 1

Advertisement