Appendix A.2.2. Attribute States Recognised For Attribute Method 1 - FieldServer FS-8700-41 Driver Manual

Simplex time recorder company - 4100 computer port protocol
Table of Contents

Advertisement

FS-8700-41 Simplex 4100 Driver Manual
Appendix A.2.2.
Attribute States recogni sed for Attribute M ethod 1
The table below reports the attribute states recognized for attribute method=1.
Attribute State
AUTOMATIC CONTROL
OUTPUT NORMAL
SELF TEST NORMAL
CORRECT DEVICE
PRIORITY 15
RANGE NORMAL
ALARM
SHORT
SHORT
ARMED
ENABLED
ON-LINE
ENABLED
NORMAL
TROUBLE
OFF
ON
Examples:
PHYSICAL STATE
The Driver recognizes 'Physical State' as attribute 2 and uses method 1 to evaluate the rest of the line. The attribute state
SHORT has a value of 8. The number 8 is stored at location 2 in the Data Array.
VALUE=77 / 0% OF ALARM / 1.0% SMOKE
The Driver recognizes 'VALUE=' as attribute 17 and uses method 2 to evaluate the rest of the line. The Dri ver stores the
values; 77, 0 and 1.0 in three consecutive locations starting at location 17. Note that there is a gap between attribute 17 and
the next attribute in the table sufficient for storing up to 3 values. The three values are seperated by slashes .
AVERAGE VALUE=75 / ALARM LEVEL=145
The Driver recognizes 'AVERAGE VALUE' as attribute 14 and uses method 3 to evaluate the rest of the line. The Driver stores
the values; 75 and 145 in two consecutive locations starting at location 14. An equal sign '=' precedes each numeric value.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Value
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
0
SHORT
Page 19 of 48