FS-8700-40 SBT FSI Driver Manual
5.3.5 Map Descriptor example 2 – Monitoring Analog Loop Devices
Analog devices on a loop can be monitored for detector voltage, sensitivity voltage and threshold voltage using three analog Map Descriptors:
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name
, Data_Array_Name
CD_Analog_Volts1
, Analog_Volts
CD_Analog_Sens1
, Analog_Sense
CD_Analog_Thres1
, Analog_Thres
Note: If necessary, use more analog Map Descriptors with other Analog_Device numbers to poll other devices on the loop.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
, Data_Array_Offset
, Function , Node_Name , Block_Number , Length , Msg_Type
, 0
, Rdbc
, Panel1
, 0
, Rdbc
, Panel1
, 0
, Rdbc
, Panel1
Use Float Data Arrays for
the analog Map
Descriptors to get the
full analog value.
Page 16 of 34
, 1
, 60
, Analog_Volts
, 1
, 60
, Analog_Sense , 0
, 1
, 60
, Analog_Thres
0 : devices 1-60
1 : devices 61-121
2 : devices 122-182
3 : devices 183-243
4 : devices 244-252
, Analog_Device , Scan_Interval
, 0
, 300s
, 300s
, 0
, 300s
Scan Interval on analog
pollers may not be shorter
than 300s to prevent
flooding the Foreign
Systems Interface.