Client Side Connection Parameterss - FieldServer FS-8700-40 Driver Manual

Sbt-fsi driver
Table of Contents

Advertisement

FS-8700-40 SBT FSI Driver Manual
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for SBT-FSI communications, the driver independent FieldServer buffers need to be declared in the
"Data Arrays" section, the destination device addresses need to be declared in the "Client Side Nodes" section, and
the data required from the Servers needs to be mapped in the "Client Side Map Descriptors" section. Details on
how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
5.1

Client Side Connection Parameterss

Section Title
Connections
Column Title
Function
Port
Specify which port the device is connected to the FieldServer
Protocol
Specify protocol used
Enables legacy or enhanced protocol.. MXL panels do not currently
support Enhanced_Protocol, so this parameter must be set to "No" for
Enhanced_Protocol
MXL. The parameter is normally set to "Yes" for XLS, but may be set to
"No" if problems are being experienced.
System_Type
Specifies Siemens Panel type
7
Block_Acks
Specifies if the driver uses block or individual command acks
Specifies if the driver should hold fire alarms until the system reset, or
Fire_Alarms_Hold*
clear on fire alarms going out
Baud*
Specify baud rate
Parity*
Specify parity
Data_Bits*
Specify data bits
Stop_Bits*
Specify stop bits
Poll _Delay*
Time between internal polls
Example
// Client Side Connections
Connections
Port
, Protocol
, Baud
P1
, SBT-FSI
, 19200
6
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.
7
Refer to the Advanced Driver Manual for usage. This function not enabled on standard driver.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
, Parity
, Data_Bits
, Poll_Delay
, Even
, 7
, 0.100s
Page 11 of 34
Legal Values
6
P1-P8, R1-R2
Cerberus,
SBT-FSI
Yes (XLS)
No (MXL)
MXL, XLS
Yes, No
Yes, No
19200
(Vendor
limitation)
Even (Vendor
limitation)
7
(Vendor
limitation)
1
(Vendor
limitation)
0-32000
seconds,
1
second

Advertisement

Table of Contents
loading

Table of Contents