Configuring The Fieldserver As A Setra Model 370 Digital Pressure; Server Side Connection Descriptors - FieldServer FS-8700-101 Driver Manual

Setra digital pressure gage model 370
Table of Contents

Advertisement

FS-8700-101_Setra Model 370 Digital Pressure Gage Manual
5.
Configuring the FieldServer as a Setra Model 370 Digital Pressure Gage
Server
For a detailed discussion on FieldServer configuration, please refer to the FieldServer
Configuration Manual. The information that follows describes how to expand upon the factory
defaults provided in the configuration files included with the FieldServer.
This section documents and describes the parameters necessary for configuring the FieldServer
to communicate with a Setra Model 370 Digital Pressure Gage Client
The configuration file tells the FieldServer about its interfaces, and the routing of data required.
In order to enable the FieldServer for Setra Model 370 Digital Pressure Gage communications,
the driver independent FieldServer buffers need to be declared in the "Data Arrays" section, the
FieldServer virtual node(s) needs to be declared in the "Server Side Nodes" section, and the
data to be provided to the Clients needs to be mapped in the "Server Side Map Descriptors"
section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the
default.
5.1.

Server Side Connection Descriptors

Section Title
Connections
Column Title
Port
Protocol
Baud*
Parity*
Data_Bits*
Stop_Bits*
Handshaking*
Server_Hold_Timeout*
Example
//
Server Side Connections
Connections
Port,
Protocol,
P8,
Setra370,
2
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
Function
Specify which port the device is
connected to the FieldServer
Specify protocol used
Specify baud rate
Specify parity
Specify data bits
Specify stop bits
Specify hardware handshaking
Specifies time FieldServer will
reserve Server side connection
while waiting for the Client side to
update data in Data_Array (if
necessary)
Baud,
9600,
Legal Values
P1-P8, R1-R2
Setra370
110 – 115200, standard
baud rates only
Even, Odd, None, Mark,
Space
7, 8
1
RTS, RTS/CTS, None
>1.0s
Parity,
Handshaking,
None,
None,
Page 13 of 23
2

Advertisement

Table of Contents
loading

Table of Contents

Save PDF