Hdd Temp - EverFocus EDR-1610A Installation & Operation Manual

Digital video recorder
Table of Contents

Advertisement

3.11.2 HDD TEMP.

WARNING SETUP MENU
FAN FAULT
BUZZER
HDD TEMP.
ALARM OUTPUT
NO HDD
ALARM DURATION
HDD FULL
NETWORK ALARM
EMAIL
STOP RECORD
The enduring HDD temperature surveillance guarantees an alarm reaction in case the
threshold value is exceeded.
There may be several reasons for HDD temperature excess:
Exceedance of the max. tolerable ambient temperature (40°C), e.g. upon
installation in an electrical cabinet with inadequate ventilation
After-effect upon fan failure
HDD defect
(1) BUZZER:
(2) ALARM OUTPUT:
(3) ALARM DURATION: PERMANENT
(4) NETWORK ALARM: YES:
(5) EMAIL:
(6) STOP RECORD
ENABLE
1
PERMANENT
NO
NO
YES
By selecting "ENABLE", the buzzer is activated upon HDD
temperature excess.
Output relay activation.
1:
Output relay switches upon alarm.
NONE:
no output relay reaction upon alarm.
This value cannot be changed, alarm is
automatically switched off after problem has
been solved.
Network alarm activated (for settings refer to
NETWORK menu)
Network alarm reception requires optional
PowerCon software.
NO:
No network alarm transmission
YES:
Alarm email transmission (for settings refer
to NETWORK menu).
NO:
No email alarm transmission.
YES:
Recording process is stopped to avoid further
temperature rise and HDD damage.
NO:
Recording process continues.
- 47 -