Server Performance Over Power Redundancy
Enable Dynamic Power Supply Engagement
Disable Chassis Power Button
Allow 110 VAC Operation
Max Power Conservation Mode
Enable Remote Power Logging 300 Managing and Monitoring Power
Remote Power Logging Interval
3.
Click Apply to save the changes.

Configuring Power Budget and Redundancy Using RACADM

NOTE: To perform power management actions, you must have Chassis Configuration Administrator privilege.
To enable and set the redundancy policy:
1.
Open a serial/Telnet/SSH text console to CMC and log in.
2.
Set properties as needed:
To select a redundancy policy, type:
racadm config -g cfgChassisPower -o
cfgChassisRedundancyPolicy <value>
where <value> is 0 (No Redundancy), 1 (AC Redundancy), 2 (Power Supply Redundancy). The default is 0.
For example, the following command sets the redundancy policy to 1:
racadm config -g cfgChassisPower -o
cfgChassisRedundancyPolicy 1
To set the power budget value, type:
racadm config -g cfgChassisPower -o
cfgChassisPowerCap <value>
where <
value > is a number between 2715–16685 representing the maximum power limit in watts. The
default is 16685.
For example, the following command sets the maximum power budget to 5400 watts:
racadm config -g cfgChassisPower -o
cfgChassisPowerCap 5400
.
To enable or disable dynamic PSU engagement, type:
racadm config -g cfgChassisPower -o
cfgChassisDynamicPSUEngagementEnable <value>
where <value> is 0 (disable), 1 (enable). The default is 0.
For example, the following command disables dynamic PSU engagement:
racadm config -g cfgChassisPower -o
cfgChassisDynamicPSUEngagementEnable 0
.
To enable the maximum power consumption mode, type:
racadm config -g cfgChassisPower -o
cfgChassisMaxPowerConservationMode 1
To restore normal operation, type:
racadm config -g cfgChassisPower -o
cfgChassisMaxPowerConservationMode 0