Optimum environment

When installing the server in a rack, select a location that meets the environmental standards described in
this section.

Space and airflow requirements

To allow for servicing and adequate airflow, observe the following space and airflow requirements when
deciding where to install a rack:
Leave a minimum clearance of 63.5 cm (25 in) in front of the rack.
Leave a minimum clearance of 76.2 cm (30 in) behind the rack.
Leave a minimum clearance of 121.9 cm (48 in) from the back of the rack to the back of another rack
or row of racks.
HP servers draw in cool air through the front door and expel warm air through the rear door. Therefore, the
front and rear rack doors must be adequately ventilated to allow ambient room air to enter the cabinet, and
the rear door must be adequately ventilated to allow the warm air to escape from the cabinet.
CAUTION:
ventilation openings.
When vertical space in the rack is not filled by a server or rack component, the gaps between the
components cause changes in airflow through the rack and across the servers. Cover all gaps with blanking
panels to maintain proper airflow.
CAUTION:
ensures proper airflow. Using a rack without blanking panels results in improper cooling that can
lead to thermal damage.
The 9000 and 10000 Series Racks provide proper server cooling from flow-through perforations in the front
and rear doors that provide 64 percent open area for ventilation.
CAUTION:
rack door insert [P/N 327281-B21 (42U) or P/N 157847-B21 (22U)] to provide proper
front-to-back airflow and cooling.
CAUTION:
adequate airflow and to prevent damage to the equipment:
Front and rear doors—If the 42U rack includes closing front and rear doors, you must allow
5,350 sq cm (830 sq in) of holes evenly distributed from top to bottom to permit adequate
airflow (equivalent to the required 64 percent open area for ventilation).
Side—The clearance between the installed rack component and the side panels of the rack
must be a minimum of 7 cm (2.75 in).
IMPORTANT:
Compaq branded 7000 series racks.
To prevent improper cooling and damage to the equipment, do not block the
Always use blanking panels to fill empty vertical spaces in the rack. This arrangement
When using a Compaq branded 7000 Series rack, you must install the high airflow
If a third-party rack is used, observe the following additional requirements to ensure
The HP ProLiant DL388 G7 Server cable management arm is not supported on
Setup 33