ETERNUS AB/HB Installation
Outlet/Socket Specifications
■
Connection Diagrams
The following diagrams show connections between the power distribution units, the ETERNUS AB/
HB and the power sockets of the distribution boards.
Do not connect just one power distribution unit to multiple ETERNUS storage systems. In addition,
do not connect just one circuit protector of a power distribution unit to multiple ETERNUS storage
systems.
When power cords are connected to a single power supply line, the connections are more secure if
a one-to-one connection is made between each power cord and circuit protector of the distribu-
tion board.
●
For Power Distribution Unit (Six Outlets) Connections
The following diagram shows an example of a power supply connection when a power distribu-
tion unit (six outlets) is used.
-
Current consumption of each outlet: 16A or less
-
Current consumption of each inlet cable: 24A or less
Figure 21 Example of a Power Supply Connection When a Power Distribution Unit (Six Outlets) Is
Used
Line 0
CP
Distribution
board
To power supply facility
PSU: Power Supply Units
CP: Circuit Protectors
ETERNUS
60-drive shelf
(4U)
Controller shelf
(4U)
CP CP CP
CP CP CP
Power distribution unit
CP
Distribution
board
To power supply facility
Line 1
46
Site Planning Guide