Digital
Scroll Control
Board
(DSC)
The DSC
board
controls
the compressor's
capacity.
(See
Fig. 19
and Table 22.)
It receives
a l-5vdc
signal from the AUX1
board
determined
by the cooling
algorithm.
The
DSC
has
direct
control
of the
compressor
and
pulses
a
solenoid
unloader
on and off to provide
a specific
capacity.
The
discharge
temperature
thermistor
(DTT)
is monitored
by the DSC
for
compressor
safety.
The
DSC
is equipped
with
an LED
(light-emitting
diode)
for diagnostics,
See the troubleshooting
section
for more details.
T3
R
.... CC
TI
C
T2
D4 D2
T6 T4 T2
P6 P4 P2
C4 C2
24 24
.,i
Power
LED
D3D1
T5T3T1
P5P3Pl
C3C1
VACCOM
{]_
(Green)
Unloader LED
Alert
LED
(Red)
Fig. 19 - Digital
Scroll Controller
(DSC)
(08659
Table
22 -- DSC Connections
DISPLAY
SENSOR
CONNECTION
NAME
POINT DESCRIPTION
LOCATION
TYPE OF I/O
PIN NUMBER
INPUTS
CTLR
Digital Scroll Ctrl Pwr
24 VAC
24VAC/24COM
Compressor
Discharge Temperature
(DTT)
Discharge line
86k thermistor
T1/T2
CAPC
Compressor
Capacity
1- 5vdc
C1/O2
Load Control Power*
19-250VA0
L1/L2
OUTPUTS
C.ALM
Scroll Compressor Alarm
Relay
A1/A2
CMRA
Compressor A Feedback
Relay
M1/M2
Digital Scroll Unloader
Compressor
Relay
U1/U2
section
Voltage
used
for contacts
M1 & M2,
U1 & U2, and VI & V2 (24 VAC