Table 17 -- Temperature
vs Resistance
Values for the DTT Thermistor
(86K at 25 °C Resistors)
Degree
C
Degree
F
Resistance
(k Ohms)
- 40
- 40
2889.60
- 65
- 61
2087.22
- 30
- 22
1522.20
-25
-16
1121.44
- 20
- 4
864.72
- 15
5
627.28
- 10
14
475.74
- 5
23
363.99
0
62
280.82
5
41
218.41
10
50
171.17
15
59
165.14
20
68
107.44
25
77
86.00
30
86
69.28
35
95
56.16
40
104
45.81
45
116
37.58
50
122
60.99
55
161
25.68
60
140
21.40
65
149
17.91
Degree
C
Degree
F
Resistance
(k Ohms)
70
158
15.07
75
167
12.76
80
176
10.79
85
185
9.20
90
194
7.87
95
206
6.77
1 O0
212
5.85
105
221
5.09
110
260
4.45
115
269
3.87
120
248
3.65
125
257
2.92
130
266
2.58
165
275
2.28
140
284
2.02
145
296
1.80
150
602
1.59
155
311
1.39
160
620
1.25
165
329
1.12
170
368
1.01
175
647
0.92
180
356
0.86
41