Low Voltage Terminal
Strip
(TB1)
This circuit board
provides
a connection
point between
the major
control boards and a majority
of the field-installed
accessories.
(See
Fig. 22 and Table
25.) The circuit breakers
for the low voltage
control
transformers,
interface
connection
for the Carrier
Comfort
Network@
(CCN) communication,
and interface
connection
for the
Local Equipment
Network
(LEN)
communications
are also located
on the low voltage
terminal
strip.
17
I
I4
I
I
J10
J11
RUN TEST
SEPARATION OFCIRCUITSTO EACH 24V TRANSFORMER M USTBEMAiNTAiNED
1
2
3
4
5
6
7
8
9
10 R Y1 Y2 W1 W2 G
C
X
Fig. 22 - Low-Voltage
Terminal
Board (LVTB)
Table 25 -- Field Connection
Terminal
Strip
TERMINAL
DISPLAY
SENSOR
CONNECTION
LABEL
NAME
POINT DESCRIPTION
LOCATION
TYPE OF I/O
PIN NUMBER
1
24 VDC Sensor Loop power
24 VDC output
JlO, 17
2
IAQ
Indoor air quality sensor
return/space
4-20
mA input
J1O, 16
3
Air quality & humidity sensor common
Ground
J1O, 15
OAQ or
Outdoor air quality sensor or
4
SP.RH
Relative humidity sensor
field installed
4-20
mA input
J1O, 14
5
RM.OC
Remote occupancy
switch
field installed
24 VAC input
J1O, 16
6
Switch power (ENTH, RM.OC, IAQ.S)
24 VAC output
JlO, 11-12
ENTH or
Outdoor enthalpy switch, or
economizer, or
7
IAQ.S
Indoor air quality switch
return/space
24 VAC input
J1 O, 9-10
Economizer commanded
position
8*
EC.CP
economizer
2-10
VDC output
J1O, 6-8
actuator (when in digital control)
9
Economizer signal common
Ground
J1O, 3-5
10"
EC.AP
Economizer position feedback
(when
economizer
communication
JlO, 1-2
in analog control)
2-10
VDC output
R
24 VAC power
24 VAC output
J11, 11-14
Y1
NOT USED
J11,10
Y2
NOT USED
Jll,
9
Wl
NOT USED
Jll,
7-8
W2
HUM
Space Humidity Switch
space
24 VAC input
J11,6
G
NOT USED
Jll,
5
C
24 VAC common
24 VAC output
J11,2-4
X
ALRM
Alarm output (normally open)
24 VAC output
J11, 1
FIRE
SHUTDOWN
FDWN
Fire shutdown switch 24 VAC output
supply/return
switch input
J12, 7
1
FIRE
SHUTDOWN
FDWN
Fire shutdown switch input
supply/return
switch input
J12, 6
2
T55
SPT
Space temperatu re (T55/56)
space
1Ok thermistor
J12, 4- 5
1-2
T55
SPTO
Space temperatu re offset (T56)
space
1Ok thermistor
J12, 3- 4
2-3
FAN STATUS
NOT USED
J12, 1-2
1-2
LEN
Local Equipment
Network (LEN)
communication
J13, 1-3, 4-5
CCN
Carrier Comfort Network (CCN)
communication
J13, 6-8, 4-5
Refer
to Third
Party
Control
section
for more
information
(08660