Advertisement
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warning or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. When you see this symbol the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal injury or death.
CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Tag disconnect switch with a suitable warning label. Turn off accessory heater power if applicable.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
Model FV4C Fan Coil units are designed for flexibility and can be used for upflow, horizontal, or downflow (kits required on manufactured and mobile home) applications. These units are designed specifically for Puronr refrigerant (R-410A) and must be used only with Puron air conditioners and heat pumps as shipped.
These units are designed to meet the low air leak requirements currently in effect. Because of this, the units need special attention in the condensate pan and drain connection area and when brazing tubing.
These units are available for application in systems of 18,000 through 60,000 Btuh nominal cooling capacities.
Factory-authorized, field-installed electric heater packages are available in 5 through 30 kW. See Product Data for available accessory kits.
Unpack unit and move to final location. Remove carton taking care not to damage unit.
Inspect equipment for damage prior to installation. File claim with shipping company if shipment is damaged or incomplete. Locate unit rating plate which contains proper installation information. Check rating plate to be sure unit matches job specifications.
Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for wiring, piping, and servicing unit.
When unit is installed over a finished ceiling and/or living area, building codes may require a field-supplied secondary condensate pan to be installed under the entire unit. Some localities may allow the alternative of running a separate, secondary condensate line. Consult local codes for additional restrictions or precautions.
When installing any fan coil over a finished ceiling and/or living area, installation of a secondary drain pan under entire unit to avoid damage to ceiling is recommended.
FV4C Fan Coils can be installed for upflow and horizontal-left applications as factory shipped. Units can be installed for horizontal-right applications with field modifications. Units may be converted for downflow applications using factory-authorized accessory kits.
NOTE:
To ensure proper drainage for horizontal installations, unit must be installed so it is within 1/8 in. (3.2mm) level of the length and width of unit.
If return air is to be ducted, install duct flush with floor. Set unit on floor over opening. Only use return-air opening provided. All return air must pass through the coil. (See Fig. 2.)
Fig. 2 - Slope Coil Unit in Upflow Application
The FV4C Fan Coil in sizes 003, 005 and 006 are available in 2--piece modular construction. Modular construction allows installer to disassemble unit into 2 components, coil box and blower box, for ease of installation. (See Fig. 3.)
Fig. 3 - Slope Coil in Horizontal-Left Application (Factory Ready)
To disassemble unit, remove rear corner brackets by removing 2 screws which secure brackets. Remove either 2 screws in each front corner of coil box, or 2 screws in blower box. Do not remove all 4 screws in each corner. Sections may now be separated by lifting top section from lower section.
To reassemble, reverse above procedure. Be certain to reinstall all fasteners when reassembling.
Be sure installation complies with all applicable building codes that may require installation of a secondary condensate pan.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Gasket kit number KFAHD0101SLP is required for horizontal slope coil conversion to maintain low air leak/low sweat performance.
Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating. Install grommets after brazing.
To convert units for horizontal right installations:
Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating.
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
The conversion of the fan coil to downflow requires special procedures for the condensate drains on both A-coil and slope units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole is plugged for all applications except downflow, but must be used for downflow.
During the conversion process, remove the plastic cap covering the vertical drains only and discard. Remove the plug from the overflow hole and discard. At completion of the downflow installation, caulk around the vertical pan fitting to door joint to retain the low air leak performance of the unit.
In this application, field conversion of the evaporator is required using accessory downflow kit along with an accessory base kit. Use fireproof resilient gasket, 1/8- to 1/4-in. (3.2 to 6.4mm) thick, between duct, unit, and floor.
NOTE:
To convert units for downflow applications, refer to Installation Instructions supplied with kit for proper installation. For slope fan coils, use kit Part No. KFADC0201SLP. For A fan coils use kit Part No. KFADC0401ACL. Use fireproof resilient gasket, 1/8- to 1/4-in. (3.2 to 6.4mm) thick, between duct, unit, and floor.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Gasket kit number KFAHD0101SLP is required for horizontal slope coil conversion to maintain low air leak/low sweat performance.
Fig. 7 - A-Coil in Horizontal-Right Application
Fig. 8 - A-Coil
Connect supply-air duct over outside of 3/4-in. (19mm) flange provided on supply-air opening. Secure duct to flange with proper fasteners for type of duct used, and seal duct-to-unit joint.
Duct connection flanges are provided on unit air discharge connection. When using FV4C units with 20-, 24-, and 30-kW electric heaters, maintain a 1-in. (25mm) clearance from combustible materials to discharge plenum and ductwork for a distance of 36 in. (914mm) from unit. Use accessory downflow base to maintain proper clearance on downflow installations.
Use flexible connectors between ductwork and unit to prevent transmission of vibration. When electric heater is installed, use heat resistant material for flexible connector between ductwork and unit at discharge connection. Ductwork passing through unconditioned space must be insulated and covered with vapor barrier.
Metal duct systems that do not have a 90 elbow and 10 ft (3m) of main duct to first branch takeoff may require internal acoustical insulation lining.
As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with National Fire Protection Association Standards 90A or B as tested by UL Standard 181 for Class 1 air ducts.
On units with a factory installed disconnect with pull--out removed, service and maintenance can be safely performed on only the load side of the control package.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Field wires on the line side of the disconnect found in the fan coil unit remain live, even when the pull-out is removed. Service and maintenance to incoming wiring cannot be performed until the main disconnect switch (remote to the unit) is turned off.
If unit contains an electric heater, remove and discard power plug from fan coil and connect male plug from heater to female plug from unit wiring harness. (See Electric Heater Installation Instructions.)
For units without electric heat:
Check all factory wiring per unit wiring diagram and inspect factory wiring connections to be sure none were loosened in transit or installation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Tag disconnect switch with a suitable warning label. Turn off accessory heater power if applicable.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
If a disconnect switch is to be mounted on unit, select a location where drill or fastener will not contact electrical or refrigerant components.
NOTE:
Before proceeding with electrical connections, make certain that supply voltage, frequency, and phase are as specified on unit rating plate.
Be sure that electrical service provided by the utility is sufficient to handle the additional load imposed by this equipment. See unit wiring label for proper field high-- and low--voltage wiring. Make all electrical connections in accordance with NEC and any local codes or ordinances that may apply. Use copper wire only. The unit must have a separate branch electric circuit with a field--supplied disconnect switch located within sight from, and readily accessible from the unit.
Refer to unit wiring instructions for recommended wiring procedures. Use No. 18 AWG color-coded, insulated (35°C minimum) wires to make low-voltage connections between thermostat and unit. If thermostat is located more than 100 ft (30m) from unit (as measured along the low-voltage wires), use No. 16 AWG color-coded, insulated (35°C minimum) wires. PCB is circuited for single-stage heater operation. When additional heater staging is desired using outdoor thermostats or Intelligent Heat Staging, remove Jumper J2 on PCB to enable staging.
Connect low-voltage leads to thermostat and outdoor unit. (See Fig. 9, 10, 11, or 12.)
Fig. 9 - FV4C Fan Coil Wiring with 1-Speed Air Conditioner
Fig. 10 - FV4C Fan Coil Wiring with 2-Speed Air Conditioner
Fig. 11 - FV4C Fan Coil Wiring with 1-Speed Heat Pump
Fig. 12 - FV4C Fan Coil Wiring with 2-Speed Puron (R-410A) Refrigerant Heat Pump
Intelligent Heat staging of the electric heat package is possible when the FV4C is installed as a part of a single-speed heat pump system using a corporate 2-speed programmable thermostat, Thermidistatt Control, or capable zoning control and any 1 of the following electric heat packages:
Relay heaters
KFCEH2901N09, KFCEH3001F15, KFCEH3101C15, KFCEH3201F20, KFCEH3301C20, KFCEH3401F24, or KFCEH3501F30.
Complete system low--voltage wiring as shown in Fig. 9, 10, 11, or 12.
NOTE:
Where local codes require thermostat wiring be routed through conduit or raceways, splices can be made inside the fan coil unit. All wiring must be NEC Class l and must be separated from incoming power leads.
A factory-authorized disconnect kit is available for installation of 0-through 10-kW applications. When electric heat packages with circuit breakers are installed, the circuit breaker can be used as a disconnect. Transformer is factory wired for 230-v operation. For 208-v applications, disconnect black wire from 230-v terminal on transformer and connect it to 208-v terminal. (See Fig. 13.)
Fig. 13 - Transformer Connections
The secondary circuit of transformer is protected by a 5-amp fuse mounted on printed-circuit board.
Do not use outdoor thermostat with Intelligent Heat Staging.
In manufactured housing applications, the Code of Federal Regulations, Title 24, Chapter XX, Part 3280.714 requires that supplemental electric heat be locked out at outdoor temperatures above 40ºF (4ºC) except for a heat pump defrost cycle. A corporate thermostat in conjunction with an outdoor sensor can be used to lock out supplemental heat above 40ºF (4ºC). Refer to thermostat instructions for details. If a non-corporate thermostat is used, an outdoor thermostat may be required.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death
According to NEC, NFPA 70, and local codes, the cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. If conduit connection uses reducing washers, a separate ground wire must be used.
NOTE:
Use UL listed conduit and conduit connector to connect supply wire(s) to unit and obtain proper grounding. Grounding may also be accomplished by using grounding lug provided in control box.
Use of dual or multiple supply circuits will require grounding of each circuit to ground lugs provided on unit and heaters.
Use accessory tubing package or field--supplied tubing of refrigerant grade. Insulate entire suction tube if field--supplied tubing is used. Tubing package has an insulated suction tube. Do not use damaged, dirty, or contaminated tubing because it may plug refrigerant flow control device.
When tubing package is used and sweat connections are made within 60 sec, coil and tubing system does not require evacuation. Always evacuate coil and field--supplied tubing to 500 microns before opening outdoor unit service valves.
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
A brazing shield MUST be used when tubing sets are being brazed to the unit connections to prevent damage to the unit surface and condensate pan fitting caps.
Units have sweat suction and liquid tube connections. Make suction tube connection first.
Consult local code requirements
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
Wrap a wet cloth around rear of fitting to prevent damage to TXV and factory-made joints.
4. Evacuate coil and tubing system to 500 microns using deepvacuum method.
To connect drains the cap openings must be removed. Use a knife to start the opening near the tab and using pliers, pull the tab to remove the disk. Clean the edge of the opening if necessary and install the condensate line. Finally caulk around the lines where they exit the fitting to retain the low leak rating of the unit.
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
The conversion of the fan coil to downflow requires special procedures for the condensate drains on both A--coil and slope units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole is plugged for all applications except downflow, but must be used for downflow. During the conversion process, remove the plastic cap covering the vertical drains only and discard. Remove the plug from the overflow hole and discard. At completion of the downflow installation, caulk around the vertical pan fitting to door joint to retain the low air leak performance of the unit.
Units are equipped with primary and secondary 3/4-in. (19mm) FPT drain connections. For proper condensate line installation see Fig. 2, 4, 5, 6, and 8.
To prevent property damage and achieve optimum drainage performance, BOTH primary and secondary drain lines should be installed and include properly-sized condensate traps. (See Fig. 14 and 16.) Factory-approved condensate traps are available. Be sure to install plastic push-in plugs in unused condensate drain fittings. It is recommended that PVC fittings be used on the plastic condensate pan. Do not over-tighten. Finger-tighten plus 1-1/2 turns. Use pipe dope.
Fig. 14 - Recommended Condensate Trap
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property
damage. Shallow running traps are inadequate and DO NOT allow proper condensate drainage. (See Fig. 15.)
Fig. 15 - Insufficient Condensate Trap
NOTE:
When connecting condensate drain lines avoid blocking filter access panel. Prime both primary and secondary condensate traps after connecting to drain pan.
NOTE:
If unit is located in or above a living space where damage may result from condensate overflow, a field--supplied external condensate pan should be installed underneath the entire unit, and a secondary condensate line (with appropriate trap) should be run from the unit into the pan.
Any condensate in this external condensate pan should be drained to a noticeable place. As an alternative to using an external condensate pan, some localities may allow the use of a separate 3/4--in. (19mm) condensate line (with appropriate trap) to a place where the condensate will be noticeable. The owner of the structure must be informed that when condensate flows from the secondary drain or external condensate pan, the unit requires servicing, or water damage will occur.
Install traps in the condensate lines as close to the coil as possible. (See Fig. 16.)
Fig. 16 - Insufficient Condensate Trap
Make sure that the outlet of each trap is below its connection to the condensate pan to prevent condensate from overflowing the drain pan. Prime all traps, test for leaks, and insulate traps if located above a living area.
Condensate drain lines should be pitched downward at a minimum of 1 in. (25mm) for every 10 ft. (3m) of length. Consult local codes for additional restrictions or precautions.
UNIT COMPONENT HAZARD
Failure to follow this caution may result in product damage.
Never operate unit without a filter. Damage to blower motor or coil may result. Factory authorized filter kits must be used when locating the filter inside the unit. For those applications where access to an internal filter is impractical, a field-supplied filter must be installed in the return duct system.
Factory authorized filters must be used when locating the filter inside the unit. (See Table 1.)
Table 1 – Filter Kits
FILTER KIT (12 PACK) | PART NUMBER | SIZE USED WITH |
KFAFK0212MED KFAFK0312LRG | 002 003, 005 | |
KFAFK0412XXL | 006 |
Refer to outdoor unit Installation Instructions for system start--up instructions and refrigerant charging method details.
Easy Select taps are used by the installer to configure a system. The ECM motor uses the selected taps to modify its operation to a pre-programmed table of airflows. (See Table 3 and 4.) Airflows are based on system size or mode of operation and those airflows are modified in response to other inputs such as the need for de-humidification. (See Fig. 17 and 18.)
Fig. 17 - Detail of FV4C Printed-Circuit Board
Fig. 18 - Detail of FV4C Printed-Circuit Board
The FV4C Fan Coil must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used.
Select heater range for size of electric heater installed
Installer must select the auxiliary heat airflow approved for application with kW size heater installed. If no heater is installed, this step can be skipped. Each select pin is marked with a range of heaters for which airflow, also marked, is approved. For increased comfort select the narrowest kW range matching the heater size, for example, 0-10 for 10-kW heater. This airflow must be greater than the minimum CFM for electric heater application with the size system installed for safe and continuous operation. (See Table 5 and 6 for airflow delivery and minimum CFM.) Note that airflow marked is the airflow which will be supplied in emergency heat mode and heating mode on air conditioners when electric heat is the primary heating source. In heat pump heating mode when electric heaters are energized, the ECM motor will run the higher of heat pump heating airflow and electric heater airflow to ensure safe heater operation. The factory selection is the largest heater range approved. (See Fig. 17, A as indicated.)
Select system size installed
The factory setting for air conditioner or heat pump size is the largest unit meant for application with the model of fan coil purchased. Installer needs to select air conditioner or heat pump size to ensure that airflow delivered falls within proper range for the size unit installed. This applies to all operational modes with the exception of electric heat modes. (See Fig. 17, B as indicated.)
Select system type installed AC or HP
The type of system must be selected:
Select Medium, Low, or High Airflow
To provide airflow at rates described above, the AC/HP ADJUST select is factory set to the nominal (nom) tap. The adjust selections HI/LO will regulate airflow supplied for all operational modes, except non--heat pump heating modes. HI provides 15% airflow over nominal unit size selected and LO provides 10% airflow below nominal unit size selected. Adjust selection options are provided to adjust airflow supplied to meet individual installation needs for such things as noise, comfort, and humidity removal. (See Fig. 17, D as indicated.)
Select desired time delay profile
Delay selections are active in cooling and heat pump heating modes only. Auxiliary heating modes have a 1 minute off delay and zero on delay programmed into the ECM motor that cannot be overridden.
Four motor operation delay profiles are provided to customize and enhance system operation. (See Fig. 17, E as indicated) Selection options are:
Select desired fan speed when thermostat is set on continuous fan
NOTE:
If installed with a 2-speed outdoor unit, do not select HI speed continuous fan. If HI is selected, low speed compression will also run HI speed possibly resulting in insufficient dehumidification.
The low-voltage circuit is fused by a board--mounted 5-amp automotive fuse placed in series with the transformer SEC2 and the R circuit. The C circuit of the transformer is referenced to chassis ground through a printed circuit run at SEC1 connected to metal standoff marked with ground symbol.
The following basic configuration of the fan coil will provide ARI rated performance of the heat pump:
(See Fig. 21 for Quick Reference Guide)
The FV4C Fan Coil provides better than average humidity control and heated air temperature. This configuration will improve the comfort provided by the heat pump system if more humidity removal or if warmer heating air is desired. While providing this improved comfort, the heat pump system will operate efficiently, but not at the published HSPF or ARI SEER efficiency.
The following fan coil configuration is recommended for maximum heating and cooling/dehumidifying comfort: (See Fig.17.)
This configuration provides the following comfort enhancements:
Electric heaters may be installed with the FV4C Fan Coil per instructions supplied with electric heater package. See unit rating plate for factory--approved electric heater kits.
NOTE:
Units installed without electric heat should have a sheet metal block--off plate covering the heater opening. This reduces air leakage and formation of exterior condensation.
The AUX and HUM terminals on the Easy Select Board are tied directly to the G terminal, and provide a 24-vac signal whenever the G terminal is energized. (See Fig. 17 and 18.) During Super Dehumidify and SuperComfort / Perfect Heat modes, the G signal is not present and the auxiliary terminals are not energized. If the installation includes the use of these operating modes, do not use these terminals to control accessories. See Electronic Air Cleaner and Humidifier sections for further information.
The AUX1 and AUX2 terminals are not always energized during blower operation, as described above. When using an electronic air cleaner with the FV4C Fan Coil, use Airflow Sensor Part No. KEAAC0101AAA. The airflow sensor turns on electronic air cleaner when the fan coil blower is operating.
Easy Select Board terminals HUM1 and HUM2 are provided for direct connection to the low--voltage control of a humidifier through a standard humidistat. (See Fig. 19.) These terminals are energized with 24vac when G thermostat signal is present. (See Fig. 20.) Alternately, the 24-vac signal may be sourced from the W and C terminal block connections when electric heaters are used as primary heating source. When using a Thermidistatt Control, Zone Perfect Plus or Comfort Zone II, the 24--vac signal may be sourced directly from the Thermidistat HUM terminal. (See Fig. 9, 10, 11, and 12.)
Fig. 19 - Humidifier Wiring
Dehumidify Capability with Standard Humidistat Connection
Latent capacities for systems using the FV4C Fan Coil are better than average systems. If increased latent capacity is an application requirement, the field wiring terminal block provides connection terminals for use of a standard humidistat. The FV4C Fan Coil will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80% of nominal cooling mode airflow. This reduction will increase the system latent capacity until the humidity falls to a level which causes the humidistat to close its contacts. When the contacts close, the airflow will return to 100% of the selected cooling airflow. To activate this mode, remove Jumper J1 and wire in a standard humidistat. (See Fig. 20.)
Fig. 20-Humidistat Wiring for De-Humidify Mode
This model fan coil is capable of responding to a signal from indoor system control (Thermidistat, zoning control) to operate in comfort control modes such as Super Dehumidify Mode. Consult literature provided with indoor system control to determine if these operating modes are available, and to see control set up instructions. No special setup or wiring of fan coil is required.
The FV4C will supply airflow in a range which is more than twice the range of a standard fan coil. It is designed to provide nominal cooling capacities at a 50°F (10°C) evaporator temperature and the required airflow which enables it to match with 4 air conditioner or heat pump system sizes. Table 2 outlines the CFM range for the different FV4C Fan Coil sizes.
(See Fig. 22 for Quick Reference Guide)
NOTE:
The indoor control used, such as Thermidistat, must be capable of providing Super Dehumidify operation mode and control must be configured as outlined in its installation instructions. Consult indoor control literature to determine if control is capable of providing Super Dehumidify inputs and for configuration instructions.
If the indoor temperature is below the temperature set point and the humidity is above the humidity set point, the Thermidistat closes circuit R to O, opens circuits R to DH and R to G, and cycles circuit R to Y/Y2 (for single speed system R to Y1, or R to Y1 and Y/Y2 for 2-speed system).
The ECM motor reads the G signal to the fan coil while the heat pump is operating, (circuit R to Y/Y2 for single speed system, R to Y1 or R to Y1 and Y/Y2 for 2--speed system), closed (24 vac). If circuit R to G is closed (24 vac), the motor will deliver airflow at the full cooling or cooling plus dehumidify mode requested value. If circuit R to G is open (0 vac) for super dehumidify mode, the motor delivers reduced airflow to maximize the humidity removal of the system while minimizing over-cooling.
Thermostat closes circuits R to G, R to Y/Y2 and/or R to Y1 with R to W/W1 or W2 (and R to O in the case of defrost).
In the event that electric heating is called for by the thermostat while the heat pump is also operating in either heating or defrost modes, the motor will modify its airflow output, if necessary, to provide an airflow which is defined as safe for the operation of the electric heater during heat pump operation. That airflow is the greater of the heat pump heating airflow and the electric heater only airflow.
ELECTRICAL SHOCK HAZARD
Failure to follow this caution may result in personal injury.
High voltage is always present at motor. Disconnect power to unit before removing or replacing connectors or servicing motor. Wait at least 5 min after disconnecting power before opening motor.
The ECM motor used with this product contains two parts: the control module and motor winding section. Do not assume the motor or module is defective if it will not start. Go through the steps described below before replacing control module, Easy Select Board or entire motor. The control module is available as a replacement part.
Turn off power and check the following:
THERMOSTAT
WIRING HARNESS
If signals check correctly and motor does not run, inspect wiring harness for loose pins or damaged plastic that could cause poor connections. If connections are good, either control module or motor is defective. If proper signals are not present, check circuit board using procedure below:
12-PIN PLUG (PL-1) ON EASY SELECT BOARD
If proper signals are not present, replace Easy Select Board. If present at board and not at 16--pin connector, wiring harness is defective.
Motor is not running on a call for heat-pump heating. System is a single-speed heat pump.
These steps can be repeated for other modes of operation.
To check Easy Select Board:
Before proceeding with module replacement, check the following to ensure motor winding section is functional. With control module removed and unplugged from winding section:
If motor winding section fails one of these tests, it is defective and must be replaced.
Refer to outdoor unit Installation Instructions for system start-up instructions and refrigerant charging method details.
For continuing high performance, and to minimize possible equipment failure, it is essential that periodic maintenance be performed on this equipment. The only required maintenance that may be performed by the consumer is filter maintenance.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect all power to unit before servicing field wires or removing control package. The disconnect (when used) on access panel does not disconnect power to the line side of disconnect, but does allow safe service to all other parts of unit. If unit does not have a disconnect, disregard the foregoing. Instead, make sure that a disconnecting means is within sight from, and is readily accessible from, the unit. Disconnect all electrical power to unit before performing any maintenance or service on it.
The minimum maintenance requirements for this equipment are as follows:
Consult Fan Coil Service Manual available from equipment distributor for maintenance procedures.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
Using the Owner's/User Manual furnished in outdoor unit, the installing technician should explain system operation to the consumer with particular emphasis on indoor fan coil operation sounds and filter maintenance.
Table 2- CFM Range for FV4C Units
FAN COIL SIZE | SYSTEM SIZES | CFM RANGE |
FV4CNF002 | 024, 030, 036 | 350-1275 |
FV4CN(B,F)003 | 024, 030, 036, 042 | 415-1475 |
FV4CN(B,F)005 | 036, 042, 048 | 425-1700 |
FV4CNB006 | 042, 048, 060 | 540-2150 |
Table 3- FV4C Fan Coil Airflow Delivery (CFM) in Cooling Mode
OPERATING MODE | ||||||||||
UNIT SIZE | OUTDOOR UNIT CAPACITY | SINGLE-SPEED APPLICATION | TWO-SPEED APPLICATION | FAN ONLY | ||||||
Nominal A/C Cooling | A/C Cooling Dehumidity | High Speed | Low Speed | Lo | Med | High | ||||
Nominal A/C Cooling | A/C Cooling Dehumidity | Nominal A/C Cooling | A/C Cooling Dehumidity | |||||||
002 | 018 024 030 036 | 525 700 875 1050 | 420 560 700 840 | - 700 - 1050 | - 560 - 840 | - 560 - 840 | - 450 - 670 | 350 350 440 525 | 420 560 700 840 | 525 700 875 1050 |
003 | 024 030 036 042 | 700 875 1050 1225 | 560 700 840 980 | 700 - 1050 - | 560 - 840 - | 560 - 840 - | 450 - 670 - | 415 440 525 610 | 560 700 840 980 | 700 875 1050 1225 |
005 | 030 036 042 048 | 875 1050 1225 1400 | 700 840 980 1120 | - 1050 - 1400 | - 840 - 1120 | - 840 - 1120 | - 670 - 895 | 440 525 610 700 | 700 840 980 1120 | 875 1050 1225 1400 |
006 | 036 042 048 060 | 1050 1225 1400 1750 | 840 980 1120 1400 | 1050 - 1400 1750 | 840 - 1120 1400 | 840 - 1120 1400 | 670 - 895 1120 | 540 610 700 875 | 840 980 1120 1400 | 1050 1225 1400 1750 |
NOTES:
Table 4 - FV4C Fan Coil Airflow Delivery (CFM) in Heat Pump Only Heating Mode
OPERATING MODE | ||||||||||
UNIT SIZE | OUTDOOR UNIT CAPACITY | SINGLE-SPEED APPLICATION | TWO-SPEED APPLICATION | FAN ONLY | ||||||
Heat Pump Comfort | Heat Pump Efficiency | High Speed | Low Speed | Lo | Med | High | ||||
Heat Pump Comfort | Heat Pump Efficiency | Heat Pump Comfort | Heat Pump Efficiency | |||||||
002 | 018 024 030 036 | 470 630 785 45 | 525 700 875 1050 | - 630 - 945 | - 700 - 1050 | - 505 - 755 | - 560 - 840 | 350 350 390 470 | 380 505 630 755 | 470 630 785 945 |
003 | 024 030 036 042 | 630 785 945 1100 | 700 875 1050 1225 | 630 - 945 - | 700 - 1050 - | 415 - 755 - | 560 - 840 - | 415 415 470 550 | 505 630 755 880 | 630 785 945 1100 |
005 | 030 036 042 048 | 785 945 1100 1260 | 875 1050 1225 1400 | - 945 - 1260 | - 1050 - 1400 | - 755 - 1010 | - 840 - 1120 | 425 470 550 630 | 630 755 880 1010 | 785 945 1100 1260 |
006 | 036 042 048 060 | 945 1100 1260 1575 | 1050 1225 1400 1750 | 945 - 1260 1575 | 1050 - 1400 1750 | 755 - 1010 1260 | 840 - 1120 1400 | 540 550 630 785 | 755 880 1010 1260 | 945 1100 1260 1575 |
NOTES:
Table 5 - FV4C Airflow Delivery (CFM)
FAN UNIT SIZE | OUTDOOR UNIT CAPACITY BTUH | ELECTRIC HEATER kW RANGE | |||||||||||
0-5 | 0-10 | 0-15 | 0-20 | ||||||||||
Lo | Nom | High | Lo | Nom | High | Lo | Nom | High | Lo | Nom | High | ||
002 | 18,000 24,000 30,000 36,000 | 625 650 815 980 | 625 725 905 1085 | 625 835 1040 1250 | 675 - - 980 | 675 725 905 1085 | - 835 1040 1250 | - 875 900 980 | - 875 900 1085 | - 875 1040 1250 | - - 1100 1100 | - - 1100 1100 | - - 1100 1250 |
003 | 24,000 30,000 36,000 42,000 | 675 815 980 1140 | 725 905 1085 1270 | 835 1040 1250 1460 | 875 875 980 1140 | 875 905 1085 1270 | - 1040 1250 1460 | - 1100 1100 1140 | - 1100 1100 1270 | - 1100 1250 1460 | - - 1225 1225 | - - 1225 1270 | - - 1250 1460 |
FAN UNIT SIZE | OUTDOOR UNIT CAPACITY BTUH | ELECTRIC HEATER kW RANGE | |||||||||||
0-10 | 0-15 | 0-20 | 0-30 | ||||||||||
Lo | Nom | High | Lo | Nom | High | Lo | Nom | High | Lo | Nom | High | ||
005 | 30,000 36,000 42,000 48,000 | 975 980 1140 1305 | 975 1085 1270 1450 | 1040 1250 1460 1665 | 1100 1100 1140 1305 | 1100 1100 1270 1450 | 1100 1250 1460 1665 | - 1250 1250 1305 | - 1250 1270 1450 | - 1250 1460 1665 | - - - 1500 | - - - 1500 | - - - 1665 |
006 | 36,000 42,000 48,000 60,000 | 1100 1140 1305 1630 | 1100 1270 1450 1810 | 1250 1460 1665 2085 | 1350 1350 1350 1630 | 1350 1350 1450 1810 | 1350 1460 1665 2085 | - 1525 1525 1630 | - 1525 1525 1810 | - 1525 1665 2085 | - - 1750 1750 | - - 1750 1810 | - - 1750 2085 |
NOTE:
Lo, NOM, and HI refer to AC, HP CFM ADJUST selection.
Airflow not recommended for heater/system size.
Table 6 - FV4C Minimum CFM for Electric Heater Application
FAN COIL UNIT | HEAT PUMP UNIT SIZE | CFM | ||||
HEATER SIZE kW | ||||||
5 | 8, 9, 10 | 15 | 18, 20 | 24, 30 | ||
002 | Heater Only 018 024 030 036 | 625 625 650 800 970 | 625 625 725 875 970 | 725 - 875 875 970 | 875 - - 1040 1040 | - - - - - |
003 | Heater Only 024 030 036 042 | 675 675 800 975 1125 | 700 875 875 975 1125 | 1050 - 1100 1100 1125 | 1050 - - 1125 1125 | - - - - - |
005 | Heater Only 018 036 042 04 | 675 800 975 1125 1305 | 700 875 975 1125 1305 | 1050 1100 1100 1125 1305 | 1050 - 1225 1225 1305 | 1400 - - - 1400 |
006 | Heater Only 018 042 048 060 | 1050 1100 1125 1300 1625 | 1050 1100 1125 1300 1625 | 1050 1350 1350 1350 1625 | 1050 1350 1350 1465 1750 | 1750 - - 1750 1750 |
NOTES:
Table 7 - Wiring connection of FV Fan Coil Wiring Harness
16-IN PLUG ON WIRING HARNESS TO MOTOR | WIRING HARNESS CONNECTION TO EASY SELECT BOARD | ||||
Pin on 16-Pin Plug | Description | Pin on 12-Pin Plug or Set-up Selection | Wire Color | Signal on Pin with Screw Terminal Jumpered to R* | |
1 | Common | Pin 9 on PL-1 | Brown | ||
2 | W1 | Pin 7 on PL-1 | Violet | 24VAC** | |
3 | Common | Auxiliary Heat Stage 1 | Pin 10 on PL-1 | Orange | |
4 | On/Off Delay Selection | On/Off Delay Selection | White | ||
5 | AC/HP Size Selection | AC/HP Size Selection | Blue | ||
6 | Y1 | Low Speed AC or HP | Pin 3 on PL-1 | Black | (-) 12VDC** |
7 | AC/HP CFM Adjust Selection | AC/HP CFM Adjust Selection | Black | ||
8 | Not Used | N/A | Not Used | ||
9 | System Type Selection | System Type Selection | Orange | ||
10 | Dehumidify | Pin 12 on PL-1 | Gray | 0V (24VAC on no call) | |
11 | Aux Heat Size Selection | Aux Heat Size Selection | Violet | ||
12 | 24v AC | Pin 8 on PL-1 | Red | 24VAC continuous | |
13 | W2 | Auxiliary Heat Stage 2 | Pin 4 on PL-1 | White | 24VAC** |
14 | Y/Y2 | Single Speed AC or HP, High Speed 2-Speed AC or HP | Pin 2 on PL-1 | Yellow | (-) 12VDC* |
15 | G | Fan | Pin 1 on PL-1 | Green | 24VAC** |
16 | Not Used | N/A | Not Used |
*Check voltages with 16-Pin Plug disconnected from motor.
**These signals will start motor.
SET-UP INSTRUCTIONS FOR WARMER HEATING TEMPERATURES AND SUPER HUMIDITY CONTROL IN COOLING
EASY SELECT BOARD
THERMIDISTAT TM CONTROL SETTINGS
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Thank you! Your question has been received!
Need Assistance?
Do you have a question about the FV4C that isn't answered in the manual? Leave your question here.