Transducer Troubleshooting; Forcing Inputs And Outputs - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Sensor
Trim
Corrective
offsets can be applied
to the space
temperature
and the
supply air temperature
sensor readings.
These corrections
are set in
the
Configuration--,TRIM
menu
for
the
display,
or
in
the
Maintenance--,TRIM
table for CCN.
See the Indoor
Air Quality
section for available
adjustments
to IAQ and OAQ sensor readings.
The
space
temperature
may
be
corrected
by entering
either
a
calibration
temperature
value
in SPT.C,
or an offset temperature
value
in SPT.T.
The supply-air
temperature
may be corrected
by
entering
either
a calibration
temperature
value
in SAT.C,
or an
offset temperature
value
in SAT.T.
The return-air
temperature
may
be corrected
by entering
either
a calibration
temperature
value in
RAT.C
or an
offset
temperature
value
in RAT.T.
Temperature
corrections
should only be made if sensor readings
are compared
to
an accurate
reference
temperature
measurement
device.
Transducer
Troubleshooting
The electronic
control
uses suction
pressure
transducers
to measure
the suction
pressure
of the refrigerant
circuits.
The pressure/voltage
characteristics
of these transducers
are in shown
in Table 18, the
5vdc power is applied
to legs A and B of the transducer
and legs B
to C represent
the voltage
drop shown in the table. The accuracy
of
these
transducers
can
be
verified
by
connecting
an
accurate
pressure
gauge to the second
refrigerant
port in the suction
line.
Forcing
Inputs and Outputs
Many
variables
may
have
their value
forced
through
CCN
or
directly
at the local display.
This can be useful
during
diagnostic
testing and also during
operation,
typically
as part of an advanced
third party
control
scheme.
Input
and output
points
that may be
forced are indicated
as 'forcible'
in the write status column
of the
display
and CCN tables.
If the user needs
to force
a variable,
follow
the same
process
as
when editing
a configuration
parameter.
A forced
variable
will be
displayed
on the Scrolling
Marquee
with
a blinking
period
"."
following
its value.
A forced
value
on Navigator
TM
accessory
is
indicated
with
a blinking
"f'.
A forced
value
on CCN
devices
is
indicated
with
"Control"
if
forced
at
the
unit
display,
or
"Supervisor"
if forced via CCN.
To remove
a local force with the
Scrolling
Marquee,
select the point with the ENTER
key and then
press the up-arrow
and down-arrow
keys simultaneously.
IMPORTANT:
In the case of a control
power
reset, any force in
effect at the time of power
reset will be cleared.
38