General Operating Sequence; Occupancy Determination - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

RH
Sensor
On
OAQ
Input
(RH.S)
This configuration
identifies
if a space
relative
humidity
sensor
is
installed
on the outdoor
air quality
(OAQ)
input.
A YES
value
enables
SP.RH
display,
A NO value
disables
SP, RH display
and
use.
Space
Humidity
Switch
(RH.SW)
This configuration
identifies
if a space
relative
humidity
switch
is
installed
on the ENTHALPY
input,
and what
status
(normally
open,
normally
closed)
the input
is when
the space
humidity
is
LOW.
Temperature
Compensated
Start Cooling Factor
This
factor
is
used
in
the
equation
of
the
Temperature
Compensated
Start Time Bias for cooling.
A setting of 0 minutes
indicates
Temperature
Compensated
Start
in
Cooling
is not
permitted.
Temperature
Compensated
Start Heating Factor
This
factor
is
used
in
the
equation
of
the
Temperature
Compensated
Start Time Bias for heating.
A setting
of 0 minutes
indicates
Temperature
Compensated
Start
in
Heating
is not
permitted.
General
Operating
Sequence
The PD unit must
be connected
to a space
temperature
sensor
T-55,
T-56,
T58 or T59 and will not operate
with a conventional
R, YI, Y2, WI, W2, G, C thermostat.
When a T-55,
T-56,
T58 or
T59
space
temperature
sensor
is connected
to the low
voltage
terminal
board as shown
in the Installation
Instructions
Manual,
the
PD
unit
will
try
to
maintain
the
Space
Temperature
(Temperatures-+AIR.T-+SPT)
at one
of four
set points:
The
Occupied
Cool
Set Point
(Setpoints-+OCSP),
the
Unoccupied
Cool
Set Point
(Setpoints--,UCSP),
Occupied
Heat
Set Point
(Setpoints--,OHSP),
or
the
Unoccupied
Heat
Set
Point
(S etpoints-+
UHSP).
Occupancy
Determination
When the building
is in occupied
mode, the occupied
set points are
active.
When the building
is in unoccupied
mode,
the unoccupied
set points
are active.
The PD control
will
switch
automatically
between
cooling
and heating
to maintain
temperature.
However,
to
minimize
unnecessary
cool to heat and heat to cool changes,
there
is a 10-minute
delay after the last stage turns off before
the control
will switch
modes.
The heating
and cooling
set points
are also
separated
by a Heat-Cool
Set Point Gap (Setpoints-,GAP)
that is
user configurable
from 2 to 10 degrees
F. This parameter
prevents
the unit from over cooling
the conditioned
space to where heating
mode
is required
or over heating
the conditioned
space
to where
cooling
mode is required.
The T55 space
temperature
sensor
senses
the temperature
in the
conditioned
space
with
no
provisions
for
adjusting
the
space
temperature
set point
at the sensor.
The T-56
space
temperature
sensor senses the temperature
in the conditioned
space
and allows
for adjustment
of the space temperature
set point by a configurable
number
of degrees
F higher or a configurable
number
of degrees
F
lower at the space temperature
sensor.
The T58 space temperature
sensor
communicates
with
the PD unit control
board
through
a
CCN
RS-485
+, -,
and
ground
connection.
The
T59
space
temperature
sensor is a T56 sensor
with an integrated
temperature
display.
A jumper
wire
is not needed
between
R and WI when
using space temperature
sensors
T55, T56, T58 or T59.
The building's
occupancy
is affected
by a number
of different
factors.
When the unit is operating
with a space temperature
sensor
(T-55,
T-56,
T-58
or T-59),
occupancy
affects the unit set points
and
the
operation
of
the
economizer.
The
factors
affecting
occupancy
are listed below
from highest
to lowest priority.
Level 1 Priority
The CCN point OCCUPIED
is forced
via an external
device
such
as a ComfortID
_ controller:
when
OCCUPIED
is forced to YES,
the unit is considered
occupied,
when
OCCUPIED
is forced
to
NO, the unit is considered
unoccupied.
If OCCUPIED
is not being
forced,
proceed
to the level 2 priority.
Level 2 Priority
Remote
Occupancy
Switch
should
be
configured
to
either
Normally
Open or Normally
Closed
when
the user would
like to
control
the occupancy
with
an external
switch.
This
switch
is
field-supplied
(24v,
single pole, single throw
[SPST]).
There
are
three possible
configurations
for the remote occupancy
switch:
1. (Configuration---_UNIT---_RM.SW
= 0) No Switch
2. (Configuration-+UNIT-+RM.SW
= 1) Normally
Open
Switch
3. (Configuration-+UNIT-+RM.SW
= 2) Normally
Closed
Switch
If the switch is configured
to No Switch (0), the switch
input value
will be ignored
and software
will proceed
to level 3 priority.
For
each type
of switch,
the appropriate
configuration
and states
are
listed in the table below.
TYPE
OF SWITCH
Occupied when
Closed or
Unoccupied when
Open
SWITCH
CONFIGURATION
Normal Open (1)
Occupied
when
Open
Normal
Closed
(2)
Unoccupied
when
Closed
Normal
Closed
(2)
STATE
OF
SWITCH
AND
STATE
OF
OCCUPANCY
Open
and
Unoccupied
Closed
and
Occupied
Open
and
Occupied
Closed
and
Occupied
IMPORTANT:
To perform
remote
occupancy,
an Economizer
Control
Board must be installed
in the unit.
Level
3
Priority
The following
occupancy
options
are determined
by the state of
Occupancy
Schedule
Number
(Configuration---,CCN---,SCH.O---,SCH_
and
the
Global
Schedule
Broadcast
(Configuration-+CCN-+BROD-+B.GS).
1. (Configuration---,CCN---,SCH.O---,SCH_
= O) The unit is
always
considered
occupied
and the programmed
schedule
is ignored.
This is the factory default.
2. (Configuration-+CCN-+SCH.O-+SCH.N
= 1-64)
Follow
the local programmed
schedule.
Schedules
I to 64 are local
within
the controller.
The 48/50PD
unit can only store one
local
schedule
and
therefore
changing
this
number
only
changes
the title of the schedule
table.
3. (Configuration--,CCN-+SCH.O-+SCH.N
=
65-99)
Follow
the global
programmed
schedule.
If the 48/50PD
unit
is
configured
as
a Global
Schedule
Broadcaster
(Configuration---,CCN---,ROD---,B.GS
=
YES),
the
unit
will follow
the unit's
programmed
schedule
and broadcast
the schedule
so that other
devices
programmed
to follow
this schedule
number
can receive
the
schedule.
If the
48/50PD
unit is not programmed
as a Global
Schedule
Broadcaster
(Configuration--,CCN--,BROD--,B.GS
= NO),
the
unit
will
receive
broadcasted
schedules
from
the
unit
programmed
to broadcast
this
schedule
number.
While
using
the
programmed
schedule,
occupancy
can
be
temporarily
switched
from
unoccupied
to
occupied
by
pressing
the override
button for approximately
3 seconds
on
the T-55,
T-56,
T-58
or T-59
space
temperature
sensor.
Override
will
only
occur
if
SPT
Override
Enabled
13