Digital Scroll Controller (Dsc) Troubleshooting - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Table 9 -- Cooling
Service Analysis
PROBLEM
Compressor
and Fan Will Not Start
Compressor
Cycles
(other than
normally
satisfying
demand).
Compressor
Operates
Continuously.
Excessive
Condenser
Pressures,
Condenser
Fans Not Operating,
Excessive
Suction
Pressure,
Suction
Pressure
Too Low.
LEGEND
CB - Circuit Breaker
DSC - Digital Scroll Controller
TXV - Thermostatic
Expansion
'Calve
VFD - X?ariable Frequency
Drive
CAUSE
Power failure.
Fuse blown
or circuit
breaker
tripped.
Check CB1 and
CB2.
Disconnect
off.
Compressor
time guard to prevent short cycling.
Occupancy
schedule
set point or supply
set point not
calling
for Cooling.
Outdoor
temperature
too low.
Active
alarm.
Insufficient
line voltage.
Active
alarm.
Unit undersized
for load.
Occupancy
schedule
set point or supply
set point too
low.
Compressor
running
at lowest capacity
Compressor
contactor
stuck on
Dirty air filters.
Low refrigerant
charge.
Condenser
coil dirty or restricted.
Loose condenser
thermistors.
Dirty condenser
coil.
Refrigerant
overcharge.
Faulty TXV.
Condenser
air restricted
or air short cycling.
Restriction
in liquid tube.
No Power to contactors.
High heat load.
Faulty TXV.
Refrigerant
overcharged.
Dirty air filters.
Low refrigerant
charge.
Faulty TXV.
Insufficient
evaporator
airflow.
Indoor Fan Running
to slow or off while compressor
is
on
Temperature
too low in conditioned
area (low
return-air
temperature).
REMEDY
Call power
company.
Replace fuse or reset circuit
breaker.
Power disconnect.
Check time guards
using ComfortLink_'
Scrolling
Marquee
also the DSC has a 2 minute
anti-short
time
Check cooling
demand
using ComfortLink
Scrolling
Marquee.
Check Compressor
Lockout
Temperature
using
ComfortLink
Scrolling
Marquee.
Check active alarms
using ComfortLink
Scrolling
Marquee
and DSC alert flash codes
Determine
cause and correct.
Check active alarms
using ComfortLink
Scrolling
Marquee
and DSC alert flash codes
Decrease
load or increase
size of unit.
Check and adjust set points
if needed.
Check cooling
demand
using ComfortLink
Scrolling
Marquee
and DSC alert flash codes.
Replace filters.
Check pressure,
locate leak, repair, evacuate,
and
recharge.
Clean coil or remove
restriction.
Tighten
thermistors.
Clean coil.
Recover
excess
refrigerant.
1.Check
TXV bulb mounting
and secure
tightly
to suction
line and insulate.
2.Replace
TXV (and filter drier) if stuck open or closed.
Determine
cause and correct.
Remove
restriction.
Fuse blown
or plug at motor
loose.
Check for sources
and eliminate
1.Check
TXV bulb mounting
and secure
tightly
to suction
line and insulate.
2.Replace
TXV (and filter drier) if stuck open or closed.
Recover
excess
refrigerant.
Replace
air filters.
Check pressure,
locate leak, repair, evacuate,
and
recharge.
1.Check
TXV bulb mounting
and secure
tightly
to suction
line and insulate.
2.Replace
TXV (and filter drier) if stuck open or closed.
Check belt tension.
Check for other
restrictions.
Check VFD display
is illuminated
and shows Auto
mode.
Power supplied
to VFD.
Check O-lOvdc
signal
present at AUXl
board.
Reset thermostat
or occupancy
schedule.
Digital
Scroll Controller
(DSC) Troubleshooting
The
48/50PD
units
are equipped
with
a digital
scroll
compressor.
The
compressor
has
a solenoid
unloader
that
is controlled
by the
digital
scroll
controller
(DSC).
This
DSC
turns
the
unloader
on
and
off
within
a 20
second
window.
The
amount
of
time
the
unloader
is on verses
off
within
that
20
seconds
depends
on the
desired
capacity.
This
means
that
the
ComfortLink
control
does
not
have
direct
control
of
the
compressor,
but
it does
however
control
the
power
to
the
DSC
and
the
signal
for
commanded
capacity.
The
DSC
has
three
LED
lights
to
help
during
troubleshooting;
green,
yellow,
and
red
The
DSC
will
run
the
compressor
unloaded
for
a half
a second
on
start
up
and
one
second
on
shutdown
to
prevent
reverse
rotation.
A
two
minute
anti-short
time
guard
is applied
by the DSC
after
shutting
the compressor
off.
The
DSC
has
an alarm
relay
output
that
is connected
to the MBB.
When
this
MBB
input
switch
is closed,
the
MBB
activates
the
T051
alert.
Check
the
LED
status
on
the
DSC
for
flash
alarm
codes
and correct
any problems.
Table
10 shows
the DSC's
Red
LED flash codes.
POWER
LED
(green)
--
indicates
voltage
is present
at the
24VAC
power
terminal.
When the 2 minute
anti-short
cycle timer
is active, the green LED will flash.
UNLOADED
LED
(yellow)
--
indicates
the unloader
solenoid
status. The LED is on when the unloader
solenoid
is energized.
ALERT
LED
(red)
--
conmmnicates
an
abnormal
system
condition
through
a unique
flash code.
All LEDs
Flashing
at the Same
Rate -- indicates
24VAC supply
is too low for operation.
All LEDs
On Solid at the Same
Time --
indicates
Digital
Scroll
Controller
failure.
Flash
Code 1 -- Reserved
for future use
Flash
Code 2 -- High Discharge
Temperature
This occurs
when the discharge
temperature
thermistor
(DTT)
has
31