Table 37 -- MODE
- OPERATING
MODES
(cont)
ITEM
(OCCDEFM
= CCN
only)
(LINKDATA
= CCN only)
EXPANSION
Occupancy
Supervisory
Current
Mode
(1 =Occup)
Current
Occup
Period
#
Time-Override
in Effect
Time-
Override
Duration
Current
Occupied
Time
Current
Unoccupied
Time
Next Occupied
Day
Next Occupied
Time
Next Unoccupied
Day
Next Unoccupied
Time
Previous
Unoccupied
Day
Previous
Unoccupied
Time
CCN - Linkage
Supervisory
Element
#
Supervisory
Bus
Supervisory
Block
Number
Average
Occup.
Heat
Stp.
Average
Occup.
Cool Stp.
Average
Unocc.
Heat Stp.
Average
Unocc.
Cool Stp.
Average
Zone
Temperature
Average
Occup.
Zone Temp
Linkage
System
Occupied?
Next Occupied
Day
Next Occupied
Time
Next Unoccupied
Day
Next Unoccupied
Time
Last Unoccupied
Day
Last Unoccupied
Time
CCN
RANGE
UNITS
TABLE/SUB-TABLE
0,1
0to
8
Yes/No
0to
4
xx.xx
xx.xx
hours
hh:mm
hh:mm
hh:mm
hh:mm
hh.mm
xxx
xxx
xxx
xxxx.x
dF
xxxx.x
dF
xxxx.x
dF
xxxx.x
dF
xxxx.x
dF
xxxx.x
dF
Yes/No
"Mon",
"Tue",
3-cha
&, "Sun"
r text
xx:xx
hh:mm
"Mon",
"Tue",
3-cha
&, "Sun"
r text
xx:xx
hh:mm
"Mon",
"Tue",
3-cha
&, "Sun"
r text
xx:xx
hh:mm
OCCDEFM
LINKDATA
CCN POINT
MODE
PER
NO
OVERLAST
OVR
HRS
STRTTIME
ENDTIME
NXTOCDAY
NXTOCTIM
NXTUNDAY
NXTUNTIM
PRVUNDAY
PRVUNTIM
SUPE-ADR
SUPE-BUS
BLOCKNUM
AOHS
AOCS
AUHS
AUCS
AZT
AOZT
LOCC
LNEXTOCD
LNEXTOCC
LNEXTUOD
LNEXTUNC
LLASTUOD
LLASTUNC
CCN
WRITE
STATUS
forcible
forcible
forcible
DISPLAY
WRITE
STATUS
ITEM
ALARMS
R.CUR
R.H!S
CURR
alarm#
(repeat
up to 25
alarms)
HIST
alarm#
(repeat
up to 20
Alarms)
Table 38 -- MODE
- ALARMS
EXPANSION
Reset All Current
Alarms
Reset Alarm
History
Currently
Active
Alarms
text string
Alarm
History
alarm#-
mm/dd/yy-
hh.mm
-text
string
RANGE
DEFAULT
Yes/No
No
Yes/No
No
CCN
TABLE/SUB-TABLE
MAINTENANCE
DISPLAY
ALARMS
ALARM
HISTORY
CCN POINT
ALRESET
ALH!SCLR
ALARM01C
-
ALARM25C
CCN WRITE
STATUS
forcible
forcible
DISPLAY
WRITE
STATUS
forcible
forcible
8O

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0550pd0648pd06

Table of Contents