Table 40 -- VFD CONFIGURATIONS
Parameter Group
APPLICATION
CRITICAL
DRIVE PARAMETERS
FOR ABB ACH550
DRIVES
Value
NOTE
Parameter
Number
9901
9902
9904
9905
9906
9907
9908
9909
1001
1002
1003
1301
1302
1401
1402
1403
1601
1608
1701
1702
1703
1704
1705
2003
2007
2008
2101
2102
2202
2203
2601
2605
2606
3006
H K30WA001 - 208/230V
I
(0) English
(1) HVAC Default
(3) Scalar : Freq
23O
Description
Language
Application
Macro
Motor Control Mode
Motor Nominal Voltage
Motor Nominal Current
Motor Nominal Frequency
Motor Nominal Speed
Motor Nominal Power
EXT1 Commands
EXT2 Commands
Direction
Minimum AI - 1
Maximum AI - 1
Relay Output 1
Relay Output 2
Relay Output 3
Run Enable
Start Enable 1
Override Set
Override Freq
Override Speed
Over Pass Code
Override
Maximum Current
Minimum
Frequency
Maximum
Frequency
Start Function
Stop Function
Accelerate Time
Decelerate Time
Flux Optimization
Volt/Freq Ratio
Switching
Frequency
Motor Thermal Time
H K30WA008-
460V
ABB Drive default
PD Product specific
setting
ABB Drive default
UNITS
Volts
Amps
Hz
RPM
HP
%
%
Hz
RPM
Amps
Hz
Hz
Seconds
Seconds
kHz
Seconds
PD Product specific
46O
setting
START-UP
PD Product specific
DATA
7.0
3.5
setting
60
ABB Drive default
PD Product specific
1725
setting
PD Product specific
2.4
setting
(1) DI - 1 Start/Stop
ABB Drive default
START/STOP/DIR
(1) DI - 1 Start/Stop
ABB Drive default
PD Product specific
(1) Forward
setting
20
ABB Drive default
ANALOG INPUTS
100
ABB Drive default
Carrier default settings
(7) Started
from PPS
RELAY OUTPUTS
(2) Run
ABB Drive default
(3) Fault (-1)
ABB Drive default
SYSTEM
(0) Not Set
ABB Drive default
CONTROL
(4) DI - 4
ABB Drive default
Carrier default settings
(3) DI - 3
from PPS
Carrier default settings
60
from PPS
Carrier default settings
OVER RIDE
1750
from PPS
Carrier default settings
0
from PPS
Carrier default settings
On
from PPS
PD Product specific
8.0
4.0
setting
LIMITS
0
ABB Drive default
60
ABB Drive default
PD Product specific
(6) Ramp
setting
START/STOP
PD Product specific
(2) Ramp
setting
30
ABB Drive default
ACCEL/DECEL
30
ABB Drive default
PD Product specific
(1) On
setting
Carrier default settings
MOTOR
(2) Squared
from PPS
Carrier default settings
8
from PPS
FAULT
Carrier default settings
FUNCTIONS
1050
from PPS
All Other Parameter Settings are ABB Drive Default Settings