Carrier 50PD05 Operating And Service Instructions page 59

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Carrier Accessory Kits
There
are specific
accessory
kits sold for various
field
installed
accessories.
These
kits
vary
based
on
model,
size,
voltage,
manufacture
date, and duct orientation.
Some of these kits include
Economizer,
Power
Exhaust,
and Electric
Heat.
Refer
to the
Controls
Quick
Set-Up
section
for
configuration
and
more
information
on these accessories.
Two-Position
Damper
The two-position
outdoor
air damper
accessory
usage depends
on
model
size
and
return
duct
orientation.
This
accessory
wires
directly
into the low voltage
circuit
for the indoor
fan control.
No
other control configuration
is needed.
Indoor
Air
Quality
The indoor
air quality
(IAQ) sensor (part no. 33ZCSENCO2)
is a
field-installed
accessory
which
measures
CO2 levels
in the
air.
When installing
this sensor,
an ECB
board
must be installed
and
the
unit
must
be
configured
for
IAQ
use
by
setting
Configuration-+AIR.Q-+IA.CF
to a value
of 1, 2, or 3. See the
Indoor Air Quality section
for more information.
TB1-2
.......
4-20
mA Input
TB1-3
.......
Sensor
Common
TB1-R
......
24 VAC Output
TB1-C
......
Common
(GND)
Outdoor Air Quality
The outdoor air quality
(OAQ)
sensor is a field-installed
accessory
that measures
('02
levels in the air. When installing
this sensor,
an
ECB board
must be installed
and the unit must be configured
for
OAQ
use by setting
Configuration-+AIR.Q-+OA.CF
to a value
of I or 2. See the Indoor Air Quality section
for more information.
TBI-4
.......
4-20
mA Input
TBI-3
.......
Sensor
Common
TB1-R
......
24 VAC Output
TB1-C
......
Common
(GND)
Smoke Detectors
The smoke
detectors
are field-installed
accessories.
These detectors
can
detect
smoke
in
either
the
return
air
(part
no.
CRSMKDET003A00)
or
supply
and
return
air
(part
no.
CRSMKSUP002A00).
When
installing
either
detector,
the unit
must
be
configured
for
fire
shutdown
by
setting
Configuration-+UNIT-+FS.SW
to normally
open (1) or normally
closed (2).
TB1-Fire
Shutdown-1
....
Dry Contact
Source
TB1-Fire
Shutdown-2
....
Discrete
Input to Board
TB1-R
................
24 VAC Output
TB1-C
................
Common
(GND)
Filter
Status
The filter status accessory (part no. CRSTATUS002B00)
is a
field-installed
accessory. This accessory detects plugged filters.
When installing this accessory, the unit must be configured for
filter status
by
setting
Configuration-+UNIT-+FL.SW
to
normally open (1) or normally closed (2). Normally open (1) is the
preferred configuration.
Filter status wires are pre-run in the unit
harness and located near the switch installation location. Refer to
the Filter Accessory Installation Instructions for more information.
Fan Status
The fan status
accessory (part no. CRSTATUS003B00)
is a
field-installed
accessory. This accessory detects when the indoor
fan is blowing air. When installing this accessory, the unit must be
configured
for
fan
status
by
setting
Configuration-+UNIT-+FN.SW
to
normally
open
(1)
or
normally
closed
(2).
Normally
open
(1)
is
the preferred
configuration. Fan status wires are pre-run in the unit harness and
located near the switch installation
location. Refer to the Fan
Accessory Installation Instructions for more information.
IMPORTANT:
The Fan Status terminals
on TB1 are NOT
to be
used.
Enthalpv
Sensors
The
enthalpy
accessories
(part
no.
CRENTSNG002A00
and
CRENTDIF002A00)
are field-installed
accessories.
The
first
accessory
(outdoor
air only) detemfines
when the enthalpy
is low
relative
to a fixed
reference.
Adding
the second
accessory
(return
air) compares
the
enthalpy
between
the
outdoor
and
return
airstreams.
In each
case, the enthalpy
4 to 20 mA
signals
are
converted
to a switch
output
which
is read by the ECB.
When
installing
this
accessory,
the
unit
must
be
configured
for
enthalpy-based
control
by
setting
Configuration-+ECON-+EN.SW
to normally
open
(1). Normal
status
is an active switch
which
tells the control
that enthalpy
is
LOW.
The actual switch
terminal
LOW
is normally
closed.
Refer
to the Enthalpy
Kit Installation
Instructions
for more information
on its installation.
Return/Supply Air Temperature
Sensor
The temperature sensor (part no. 33ZCSENSAT)
is a field-installed
accessory
which
may be installed
on the common
return
air duct
and/or the common
supply
air duct near the unit.
The duct supply
air temperature
(SAT) may be used to replace
the SAT sensor
that
is internal
to the unit. A supply duct SAT measurement
is valid for
heating
mode
display
while
the factory-standard
internal
SAT is
not valid
for heating
due to its location
upstream
of the heating
section.
When
installing
the supply
duct SAT, the unit must
be
configured
by setting
Configuration--+UNIT--+SATJI
to ENBL.
A SAT sensor in the supply
duct is the preferred
configuration
for
systems
with
Carrier
variable
volume
and temperature
(VVT®)
accessory
controls.
Space
Humidistat
The
Space
Humidistat
(part
no.
--HL--38MG-029)
is a wall
mounted
device
with
an adjustable
setpoint
to control
humidity
levels.
The humidistat
input
is provided
on the field connection
terminal
board.
The
Space
Humidity
Switch
configuration,
Configuration-_UNIT-_RH.SW,
identifies
the normally
open
or
normally
closed status of this input at LOW humidity.
TB1-R
......
24 VAC Dry Contact
Source
TB1-W2
.....
Discrete
Input to Board
Space
Humidity
Sensor
The space
relative
humidity
sensor
(part
no. 33ZCSENDRH-01
duct mount
or 33ZCSENSRH-01
wall mount)
is a field-installed
accessory.
The space relative
humidity
(RHS)
may be selected
for
use if the outdoor
air quality
sensor
(OAQ)
is not used
and an
economizer
board
is
installed.
When
installing
the
relative
humidity
sensor,
the
unit
must
be
configured
by
setting
Configuration
-_UNIT-_RH.S
to YES.
TBI-1
.......
24 VDC Loop Power
TB1-4
.......
4-20 mA Input Signal
SERVICE
ELECTRICALSHOCK
HAZARD
Failure to follow this warning could cause personal
iniury or death.
Before performing
service or maintenance
operations
on unit, turn off main power switch to unit and install
lockout tag. Ensure electrical service to rooftop unit
agrees with voltage and amperage listed on the unit
rating plate.
59