Temperature Compensated Start - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

willnotbeinterrupted
tothe burners and heating willcontinue.
Once m odified, thefanondelay will notchange back to 45
seconds
unless power isreset tothe control. When t he indoor fan
turns o nafter the 40or45second delay t he indoor fan willrunat
100% fan speed.
Gas Heat Staging
When additional
heat is required,
power
is supplied
to the second
stage of the main gas valve.
When
the space
temperature
is 0.5F
above
the
Occupied
Heat
Set
Point
(Setpoint-+OHSP)
or
Unoccupied
Heat Set Point (Setpoint-+UHSP)
power
is removed
from the second
stage of the main gas valve
and to the IGC Wl
terminal.
Both
stage
1 and stage
2 of the
gas
valve
closes,
interrupting
the flow of gas to the main burners.
Gas Heat Shut Down
If power
to the IGC Wl
terminal lasted
less than 1 minute,
the
heating
cycle
will not
ternfinate
until
1 nfinute
after
power
is
applied
to
the
Wl
ternfinal
of the
IGC
board.
If the
over
temperature
linfit opens
after the indoor motor is stopped
within
10
nfinutes
of Wl
beconfing
inactive,
on the next cycle the time will
be extended
by 15 seconds.
The maximum
delay
is 3 nfinutes.
Once
modified,
the
fan off delay
will
not change
back
to 45
seconds
unless
power
is reset to the control.
A LED
indicator
is
provided
on the IGC to monitor
operation.
The IGC is located
in
the gas burner
section
and can be accessed
by opening
the gas
access door.
During
normal
operation,
the LED
is continuously
on.
Gas Heat with Economizer
When there is a call for heat as described
above the indoor
fan will
operate
at
the
Supply
Fan
Maximum
Speed
(Configuration--_UNIT--_FS_X)
configuration
setting
and the
econonfizer
outdoor
air damper
will move to the Econ Min at Max
Fan
Speed
(Configuration--_ECON--_MP_X)
position.
The
econonfizer
outdoor
air damper
is closed when
the indoor
fan is
not operating.
Electric Heating Mode Using Space Temperature
Sensor T55, T56, or T58 (50PD Units Only)
For electric
heat units with factory
installed
electric
heat, the Type
of
Heat
Installed
(Configuration--,HEAT--,HT.T¥)
will
be
factory
set to a value
of 2
and
the
Number
of Heat
Stages
(Configuration--,HEAT--,N.HTR)
will be factory
set to match the
installed
heater.
If electric
heat is installed
in the field the value for
Number
of Heat Stages
(Configuration-+HEAT-+N.HTR)
must
be changed to match the number
of heat stages installed.
Heat will not operate
if the outdoor
temperature
is greater
that the
value
configured
for
the
Heating
Lockout
Temperature
(Configuration-+HEAT-+HT_LO),
Heat
Minimum
On
Time
(Configuration-+HEAT-+MRTJt)
and Heat Minimum
Off Time
(Configuration-+HEAT-+MOT.H).
Timeguards
apply
to both
stages of heating.
Factory
defaults
values are 2 minute
s ON and 2
nfinutes
OFF.
If the indoor
fan control
is configured
to cycle with
the heating
demand
by setting
Fan ON When
Occupied
Heat
Minimum
On
Time (Configuration-+UNIT--.OC.FN)
to NO, the fan will stop
after
a
delay
configured
by
Fan-off
Delay,
Elect
Heat
(Configuration-+HEAT-+FOD.E).
The
factory
default
for
Fan-off
Delay,
Elect
Heat
(Configuration--+HEAT--+FOD_E)
is
30 seconds.
The electronic
control
uses information
from
the space
sensor
to
deternfine
the number
of heat stages required.
Once the number
of
stages needed
for heating
is deternfined,
either Heat Stage
1 Relay
(Outputs-+HEAT--,HT.1),
or
Heat
Stage
1
Relay
(Outputs-+HEAT-+HT.1)
and
Heat
Stage
2
Relay
(Outputs-+HEAT-+HT.2)
outputs
will be turned
on.
See Gas
Heating
Mode
Using
Space
Temperature
Sensor
for
more
information.
Supply-Air
Temperature
Sensor
(SAT)
The
SAT
Heat
Mode
Sensing
(Configuration--,HEAT--,SAT--,SATart)
affects
the
Supply
Air
Temperature
(Temperatures-,AIR.T-,SAT)
value displayed.
This
configuration
is accessible
via the Scrolling
Marquee
on the SAT
Heat Mode
Sensing
(Configuration--,HEAT--,SAT--,SATart).
When
the
SAT
Heat
Mode
Sensing
(Configuration--,HEAT--,SAT--,SATart)
=DSBL,
the Supply
Air
Temperature
(Temperatures-+AIR.T-+SAT)
value
on
the
Scrolling
Marquee
and the CCN tables will be forced to zero when
heat outputs
come ON and for 5 nfinutes
after.
The default
Supply
Air Temperature
(Temperatures-+AIR.T-+SAT)
location
is at the
fan inlet, upstream
of the heat section.
When
the
SAT
Heat
Mode
Sensing
(Configuration--+HEAT--+SAT--+SATatI)
= ENBL,
the
Supply
Air Temperature
(Temperatures-+AIR.T-+SAT)
sensor reading
is
displayed
at
the Scrolling
Marquee
and the CCN
tables
during
heating
mode.
This setting should only be used if the original
SAT
sensor
wires are removed
from
the Main Base Board
(MBB)
and
replaced
by an accessory
SAT sensor
located
in the supply
duct
downstream
of the heat section.
There
are then
two supply
air
temperature
limits that become
active,
the Maximum
SAT Lower
Level
(Configuration--+HEAT--+SAT--+SAM_L)
the
Maximum
SAT
Upper
Level
(Configuration-+HEAT-+SAT-+SAM.U).
Any
time
the supply
air temperature
rises above
the Maximum
SAT Lower
Level
(Configuration--+HEAT--+SAT--+SAM_L)
the
heat
staging
will
be
linfited
to
what
is currently
on
and
no
additional
stages can be added until the supply
air temperature
falls
below
the
Maximum
SAT
Lower
Level
(Configuration-+HEAT-+SAT-+SAM.L).
If
the
supply
air
temperature
rises
above
the
Maximum
SAT
Upper
Level
(Configuration-+HEAT-+SAT-+SAM.U),
then
heating
will be
reduced
by removing
a heat stage.
That stage can not be added
again
until
the
Supply
Air
Temperature
(Temperatures-+AIR.T-+SAT)
falls
below
the
Maximum
SAT
Lower
Level
(Configuration--+HEAT--+SAT--+SAM_L).
If the
supply
air temperature
stays
above
the
Maximum
SAT
Upper
Level
(Configuration--,HEAT--,SAT--,SAM.U),
then
another
stage
will
be
removed
after
the
Heat
Stage
Decrease
Time
(Configuration--+HEAT--+H39EC).
Temperature
Compensated
Start
This
logic is used when
the unit is in the unoccupied
state. The
control
will
calculate
early
Start
Bias
time
based
on
Space
Temperature
deviation
from the occupied
cooling
and heating
set
points.
This will allow
the control
to start the unit so that the space
is at conditioned
levels
when
the occupied
period
starts.
This is
required
for ASHRAE
90.1 compliance.
Setting Up the System
The settings
for temperature compensated
start can be found
in the
local display
under Configuration-+UNIT.
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
TCS.C
Temp.Cmp.Strt.Cool
Factr
0 - 60
min
TCSTCOOL
TCS.H
Temp.Cmp.Strt.Heat
Factr
0 - 60
min
TCSTHEAT
Temp
Comp
Strt
Cool Factr
(TCS.C)
This is the factor for the start time bias equation for cooling.
Temp
Comp
Strt
Heat Factr
(TCS.H)
This is the factor for the start time bias equation for heating.
IMPORTANT:
Temperature compensated start is disabled when
these factors are set to 0.
22