Accessory Installation; Orifice Change (48Pd Only); Gas Heat (48Pd Only); Controls Quick Set-Up - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Accessory
Installation
Check
to make
sure that all accessories
including
sensors
have
been installed
and wired
as required
by the instructions
and unit
wiring diagrams.
Orifice
Change
(48PD Only)
This unit is factory
assembled
for heating
operation
using
natural
gas at an elevation
from sea level to 2000 ft.
Use accessory
high
altitude
kit when
installing
this unit
at an
elevation
of 2000 to 7000 ft. For elevations
above 7000 ft, refer to
High
Altitude
section
to identify
the correct
orifice
size for the
elevation.
Purchase
these
orifices
from
your local
Carrier
dealer.
Follow
instructions
in accessory
Installation
Instructions
to install
the correct
orifices.
Use
accessory
LP
(liquid
propane)
gas
conversion
kit
when
converting
this unit for use with LP fuel usage for elevations
up
to 7000
ft. For elevations
above
7000
ft, refer to High Altitude
section
to
identify
the
correct
orifice
size
for
the
elevation.
Purchase
these
orifices
from
your
local
Carrier
dealer.
Follow
instructions
in
accessory
Installation
Instructions
to install
the
correct orifices.
Gas Heat (48PD Only)
Verify gas pressures
before turning
on heat as follows:
1. Turn off field-supplied
manual
gas stop, located
external
to
unit.
2. Connect
pressure
gauge
to supply
gas
t@,
located
on
field-supplied
manual
shutoff valve. (See F ig. 5.)
3. Connect
pressure
gauge to manifold
pressure
t@.
4. Turn on field-supplied
manual
gas stop. Enter
Service
Test
mode
by setting
Serrice
Test-_TEST
to "ON"
using
the
Scrolling
Marquee
display.
Use the Service
Test feature
to
set Serriee
Test_HEAT_HT.1
to ON (first stage of heat)
using the Scrolling
Marquee.
GAS
SUPPLY
UNION
Fig. 5 - Field
Gas Piping
C06323
5. After the unit has run for several nfinutes,
verify the supply
gas pressure
is between
5.5-in.
wg to 13.0-in.
wg, and the
manifold
pressure
is 3.50-in.
wg on sizes 03-14
and 3.00
on size 16. If manifold
pressure
must be adjusted,
refer to
Gas Valve Adjustment
section.
IMPORTANT:
Supply
gas pressure
must not exceed
13.0-in.
wg.
6. Set Service
Test-+HEAT-+HT.1
to OFF
using
Scrolling
Marquee,
7. Exit Service
Test mode
by setting
Selwice
Test-+TEST
to
"OFF"
using the Scrolling
Marquee,
CONTROLS
QUICK
SET-UP
The following
information
will provide
a quick
guide to setting up
and configuring
the
48/50PD
series
units
with
ComfortLink
T'_
controls.
Unit
controls
are
pre-configured
at the
factory
for
factory-installed
options.
Field-installed
accessories
will
require
configuration
at start-up.
Service
Test is recommended
for initial
start-up.
Additionally,
specific
job
requirements
may
require
changes
to default
configuration
values.
See the CCN and Display
parameter
tables
and other sections
of these instructions
for more
details.
Control
Set Point and Configuration
Log
During
start up, accessory
installation,
and equipment
service
set
points
and/or configuration
changes
might have to be made.
When
setting
set
points
or
changing
configuration
settings,
documentation
is recommended.
The Control
Log starting
on page
106 should be filled out and left with the unit at all times. A copy
should
also be provided
to the equipment
owner.
Standard
Unit Control
There
are two different
applications
these
units can be applied
to,
Displacement
Ventilation
and
Single
Zone
VAV.
For
either
application
a direct
wired
space
sensor
can
be
used
or
a
conmmnicating
sensor/thermostat
can be used.
Installation
of an
accessory
supply
air temperature
(SAT) sensor in the supply
duct is
recommended
when using a communication
type control.
A supply
duct SAT measurement
is valid for heating
mode display, while the
factory-standard
internal
SAT is not valid
for heating
due to its
location
upstream
of the
heating
section.
When
installing
the
supply
duct SAT, the heating
mode
display
is enabled
by setting
Configuration---,HEAT---,SAT---,SAT.H
to ENBL.
There
are several
configurations
that
should
be
considered
for
Displacement
Ventilation
or Single Zone VAV applications.
Table
3
shows
these
configuration
defaults
and
specific
application
settings.
These settings
typical
values
and should
be adjusted
for
each actual specific unit application.
Refer to the Operation
section
for more
detail
on these
configurations
and how they
effect the
units operation.
IMPORTANT:
Multiple
zoning
application
is not recommended
at this time with the PD product.
Space
Temperature
Sensor
Control--Direct
Wired
(T-55,
T-56,
or T-59)
Wire accessory
space
temperature
sensor(s)
to the T-55
terminals
on the field connection
terminal
board
located
at the unit control
box. No configuration
is required
when installing
a T-55,
T-56,
or
T-59.
Refer
to Field-Installed
Accessories
section
for additional
information.
T-58
Communicating
Thermostat
Install
the
T-58
communicating
thermostat.
Connect
the
CCN
communication
bus from the T-58
to the CCN terminals
on the
field
connection
terminal
board
located
at the unit control
box.
Configure
the unit's
CCN
communication
element
number,
bus
number,
and baud rate. Configure
the T-58's
CCN communication
bus number
and baud rate the same as the unit, while
the element
number
has to be different.
Configure
the T-58
to send SPT to the
unit's
element
number.
Refer
to the Field-Installed
Accessories
section
for additional
information.