Bacnet Communication Option Wiring; Wiring The Upc Open Controller To The Ms/Tp Network; Ms/Tp Wiring Recommendations - Carrier WeatherMaker 48A 020 Installation Instructions Manual

Single package gas heating/electric cooling rooftop units with comfortlink controls and puron refrigerant r-410a
Table of Contents

Advertisement

BACnet
®1
Communication Option Wiring
WIRING THE UPC OPEN CONTROLLER TO THE MS/TP
NETWORK
The UPC Open controller communicates using BACnet on an
MS/TP network segment communications at 9600 bps, 19.2 kbps,
38.4 kbps, or 76.8 kbps.
Wire the controllers on an MS/TP network segment in a daisy-
chain configuration. Wire specifications for the cable are 22 AWG
(American Wire Gauge) or 24 AWG, low-capacitance, twisted,
stranded, shielded copper wire. The maximum length is 2000 ft.
Install a BT485 terminator on the first and last controller on a net-
work segment to add bias and prevent signal distortions due to
echoing. See Fig. 48-50.
To wire the UPC Open controller to the BAS network:
1.
Pull the screw terminal connector from the controller's BAS
Port.
2.
Check the communications wiring for shorts and grounds.
3.
Connect the communications wiring to the BAS port's screw
terminals labeled Net +, Net -, and Shield.
1. Third-party trademarks and logos are the property of their respective
owners.
BT485
Terminator
BACNET
Connection
(BAS PORT)
Tx1 LED
Rx1 LED
Tx2 LED
Rx2 LED
EIA-485
Jumpers
RNET
Input
NOTE: Use the same polarity throughout the network segment.
4.
Insert the power screw terminal connector into the UPC
Open controller's power terminals if they are not currently
connected.
5.
Verify communication with the network by viewing a module
status report. Perform a Modstat using the i-Vu tools Field
Assistant.
To install a BT485 terminator, push the BT485 terminator on to
the BT485 connector located near the BACnet connector.
NOTE: The BT485 terminator has no polarity associated with it.
To order a BT485 terminator, consult Commercial Products i-Vu
Open Control System Master Prices.

MS/TP WIRING RECOMMENDATIONS

Recommendations are shown in Tables 11 and 12. The wire
jacket and UL temperature rating specifications list two accept-
able alternatives. The Halar
perature rating and a tougher outer jacket than the SmokeGard
specification, and it is appropriate for use in applications where
the user is concerned about abrasion. The Halar jacket is also
less likely to crack in extremely low temperatures.
NOTE: Use the specified type of wire and cable for maximum sig-
nal integrity.
Fig. 48 — UPC Open Controller
36
®1
specification has a higher tem-
Power LED
BACNET
BAUD Rate
Dip Switches
Address
Rotary
Switches
Run LED
Error LED
®
™1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Weathermaker 48a 025Weathermaker 48a 027Weathermaker 48a 030Weathermaker 48a 035Weathermaker 48a 040Weathermaker 48a 050 ... Show all

Table of Contents